| Outside
Plant Corrosion Consideration
UNITED STATES OF DEPARTMENT
OF AGRICULTURE
Rural Utilities Service
BULLETIN 1751F-815
SUBJECT: Electrical Protection
of Outside Plant
TO: All Telecommunications
Borrowers
RUS Telecommunications Staff
EFFECTIVE DATE: Date of
Approval
EXPIRATION DATE: Seven years
from effective date
OFFICE OF PRIMARY INTEREST:
Engineering Standards Branch, Telecommunications Standards
Division
PREVIOUS INSTRUCTIONS: This
bulletin replaces Telecommunications Engineering and Construction
Manual (TE&CM) Section 815, Number 4, issued April 1969;
Section 816, Number 3, issued July 1969; Addendum No. 1 for
Section 816, issued January 1971; Addendum No. 2 for Section
816, issued December 1972; Section 817, Number 1, issued March
1980.
FILING INSTRUCTIONS: Discard
TE&CM Sections 815, 816, Addenda 1 and 2 for Section 816,
and 817 and replace them with this Bulletin. File this bulletin
with 7 CFR 1751 and RUSNET.
PURPOSE: To provide information concerning
the electrical protection principles for aerial and buried
cable along with information on effective grounding of cable
shields. It describes the normal methods for protecting aerial
circuits from lightning and power contacts by means of arresters,
shield grounding, and shield bonding.
___________________________ ___________
Administrator Date
TABLE OF CONTENTS
1. DISTURBING POTENTIALS 4
1.1 Lightning 4
1.2 Power Contacts 4
2. PROTECTION PRINCIPLES 5
2.1 Lightning Protection 5
2.2 Power Contact Protection 5
3. LIGHTNING PROTECTION FOR PLASTIC-INSULATED CABLE 5
3.1 Surge Dielectric Strength 5
3.2 Protection of PIC Cable 6
4. BONDING AND GROUNDING FOR POWER CONTACT PROTECTION 8
4.1 Bonding at Power Crossings 8
4.2 Bonding in Joint Use or Joint Occupancy 9
5. MISCELLANEOUS SITUATIONS 10
5.1 Underground/Buried Cable Dips in Aerial Cable Runs 10
5.2 Protection at Loading Points 10
5.3 Buffer Protection 10
5.3 Buffer Protection 10
5.4 Pole Lightning Protection Wires 11
6. ELECTRICAL PROTECTION FOR BURIED/UNDERGROUND CABLE 11
6.1 Plastic-Insulated Conductor (PIC) Cable and Wire 11
6.2 Lightning Protection 11
6.3 Power Contact Protection 12
7. LIGHTNING PROTECTION FOR BURIED/UNDERGROUND PLANT 13
7.1 Dielectric Protection of Buried/Underground Plant 13
7.2 Facilities Serving Severely Exposed Stations 13
7.3 Bonding/Grounding of Buried Wire and Cable Shields 13
8. POWER CONTACT PROTECTION FOR BURIED/UNDERGROUND PLANT 14
8.1 Aerial Inserts 14
8.2 Aerial Line Extensions 15
8.3 Aerial Drop Wires Connected to Buried Plant 16
9. GROUNDING OF BURIED WIRE AND CABLE SHIELDS 16
9.1 Grounding at Junctions 16
10. METALLIC HOUSINGS ON VERTICAL POWER POLES 16
10.1 Bonding 16
10.2 When Carrier Equipment is not Grounded 16
11. EFFECTIVE GROUNDING OF CABLE SHIELDS 17
11.1 General 17
11.2 The Purpose of Grounding Cable Shields 17
11.3 The Application of an Effective Grounding System 17
11.4 Isolating Damage Caused by a Lightning Stroke 17
11.5 Obtaining a 25 Ohm Ground 17
12. EFFECTIVE GROUNDING THEORY 18
12.1 Effective Grounding 18
12.2 Spacing of Electrodes 18
12.3 Selection of Electrode 18
FIGURES SECTION (NOT AVAILABLE ON RUSNET)
Figure 1: Lightning Damage Probability Map
19
INDEX:
Protection
Protection, Electrical
Protection, Outside Plant
ABBREVIATIONS
ANSI American National Standards Institute
Protection, Outside Plant
AWG American Wire Gauge
AWG American Wire Gauge
CEGB Cable Entrance Ground Bar
GPR Ground Potential Rise
GPR Ground Potential Rise
MGB Master Ground Bar
MGB Master Ground Bar
MGN Multigrounded Neutral
MGN Multigrounded Neutral
NEC National Electrical Code
NESC National Electrical Safety Code
NEXT Near-end Crosstalk
NFPA National Fire Protection Association
PCM Pulse Code Modulation
PIC Plastic-Insulated Conductor
PM2A Ground Wire Assembly Unit
TE&CM Telecommunications Engineering and Construction
Manual
DEFINITIONS
Cable A group of insulated
conductors formed into a compact core and covered with a protective
sheath.
Non-current carrying conductors
Non-telecommunications conductive materials such as metallic
cable shields and strength members, metallic cable lashing
wires, guy wires, and cable support wires, etc.
Plastic-insulated conductor (PIC)
cable Cable consisting of conductors covered with
an extruded coating of plastic.
Sheath The nonmetallic outer
covering over the shield of certain types of cables.
Shield The metallic components
of a cable sheath that help to minimize outside electrical
interference in cable conductors and that help to direct lightning
and power cross discharge currents to ground.
1. DISTURBING POTENTIALS
1.1 Lightning: Lightning
is a transient discharge between a charged cloud and the earth
or another cloud, involving high peak currents (several tens
of thousands to more than a 100,000 amperes) usually lasting
a few hundred microseconds. Lightning surges in cable plant
may occasionally arise because of direct strokes to pole tops
or to the cable itself. Successful protective measures against
damage are usually not practicable for direct lightning strokes
to elements of telephone cable plant. Fortunately, however,
lightning disturbances more commonly appear in cable plant
in lower energy levels by conduction from connecting distribution
wire, by induction from nearby strokes-to-earth, by conduction
from the earth at or near the stroke point to the cable through
guys or pole grounding wires, or because of a rise in ground
potential at nearby grounded points such as station protectors.
If adequate protective measures are not taken, lightning discharges
may result in the breakdown of the insulating materials between
cable conductors and the grounded metallic cable shields or
between the conductors themselves. The effect of dielectric
failure on service outage will depend on the magnitude and
duration of the surge and the susceptibility of the materials
involved to permanent damage, such as melting of the conductor
and conductor insulation or carbonization of the conductor
insulation.
1.1.1 Excessive lightning surge currents can
cause telecommunications conductors to fuse open. The use
of improved plastic insulation, however, has increased the
dielectric strength of cable conductors to the point at which
dielectric failure seldom occurs. The dielectric strength
of cable causes the current surges to flow through the conductors
rather than being bypassed through conductor insulation. As
a result, lightning damage to plastic cable plant is more
likely to be caused by conductor fusing rather than from dielectric
failure.
1.2 Power Contacts : Mutual
association of telephone cable (or wire) facilities with power
distribution circuits, as a result of joint use or joint occupancy
of poles or at crossings, involves the possibility of incidental
electrical contacts between these systems. Such electrical
contacts usually are caused by severe mechanical stresses
produced by high wind, heavy ice and snow loads, or combinations
of these factors. Although peak currents in cable plant as
a result of such contacts are likely to be in the order of
hundreds rather than thousands of amperes, their duration
is in the order of seconds rather than microseconds. Consequently,
power contacts are likely to subject telephone plant to heating
and burning, as well as dielectric stress. Power contacts
with metal shielded cable and strand may occasionally burn
down cable because of resulting arcing and current flow, or
more likely may only generate sufficient enough current flow
in telecommunications conductors to result in fusing of conductors.
Fortunately, however, the frequency of power contacts is much
lower than that of lightning interference.
2. PROTECTION PRINCIPLES
2.1 Lightning Protection :
2.1.1 Direct lightning strokes to cable plant
are likely to cause extensive damage because of the magnitude
of the currents involved. However, because the cost for total
protection, if even possible, would be immense and because
such strokes occur so infrequently, protection against direct
strokes is impracticable.
2.1.2 Lightning surges may also reach the
conductors and/or shields of aerial cable by currents conducted
from non-cable plant, by induction from nearby strokes-to-ground,
and by currents developed because of rise in ground potential
at stroke points near station protector installations. (The
term "non-cable plant" as used here refers to wire circuit
facilities not enclosed in a metal shield, such as overhead
drop wires.) Cables having plastic-insulated conductors do
not require protective measures except in unusual circumstances
as outlined in subsequent paragraphs.
2.1.3 To prevent dielectric failure of the
cable conductor insulation (by cable design), all conducting
elements of a cable installation have to be at the same potential.
The shields of all aerial cable sections should be bonded
together and to connecting underground or buried cable shields
and to the central office ground. Cable support strands (messengers)
should be electrically continuous and cable shields should
be bonded to the support strands (messengers) at appropriate
intervals.
2.2 Power Contact Protection :
Important protective construction practices also consist of
providing low impedance paths to ground which will aid in
rapid de-energization of a power line in the event of a power
contact. Such grounding is also required by the National Electrical
Safety Code (NESC1).
3. LIGHTNING PROTECTION FOR PLASTIC-INSULATED
CABLE
3.1 Surge Dielectric Strength :
The surge dielectric strength of cable utilizing plastic-insulated
conductors is conservatively considered for engineering design
purposes to be as follows:
| SURGE DIELECTRIC
STRENGTH |
| INSULATOR TYPE |
CONDUCTOR-TO-CONDUCTOR |
CORE-TO-SHIELD |
| SOLID GEL FILLED |
20 kV |
35 kV |
| GEL FILLED, EXPANDED |
15 kV |
25 kV |
Cables having dielectric strengths of these
magnitudes will in most cases be free from damage by lightning.
The relative immunity of PIC cable without arresters (except
in special circumstances) to lightning damage has been well
established by experience in the Bell Systems and RUS borrower
systems over a period of many years.
3.2 Protection of PIC Cable :
The protection of PIC cable in all areas normally should consist
of: (1) bonding and grounding cable shields at the central
office, (2) maintaining electrical continuity of the shield,
(3) bonding cable shields to support strands (messengers),
(4) grounding of cable shields (in aerial circuits via grounding
messengers, etc.,) (5) providing gas tubes or the equivalent
at junctions with facilities serving severely exposed stations,
(6) protecting against fusing of cable conductors, (7) complying
with the NEC 2 at service drops, and (8) providing supplementary
protection measures at known severe exposure locations.
3.2.1 Bonding and Grounding Cable
Shields at Central Office s: The shields and other
metallic members of plant entering a central office should
be bonded to each other and to the central office ground.
This bonding helps to minimize harmful differences of potential
between the various cables entering the central office. RUS
requires that special provisions be undertaken for bonding
and grounding of outside plant cable shields, metallic armor,
etc., with terminating cables in a central office. Basically,
non-current carrying metallic outside plant items (shields,
armor, strength members, etc.,) are all bonded together in
a entering cable vault and they are in turn bonded to a Cable
Entrance Ground Bar (CEGB) installed within the vault. The
CEGB is, in turn, bonded to the office's Master Ground Bar
and the elaborate grounding provisioning established at the
office. The shields of the office's terminating cables are
(deliberately) electrically isolated in the cable vault and
connected to the office ground only at their other end, at
the office mainframe ground bar. The purpose of this grounding
and bonding arrangement is to divert any incoming surges that
may be on the outside plant cable shields, armor, etc., directly
to ground and not provide a path for these surges to make
it directly to other parts of the mainframe. For more detail
on these special central office procedures, readers should
refer to TE&CM Section 810 (proposed conversion to RUS
Bulletin 1751F-810).
3.2.2 Maintaining Electrical Continuity
of Shields : It is important that electrical continuity
of aerial cable shields be maintained and that such shields
be bonded to any connecting buried or underground cable shields
in order to provide a path to ground for lightning and power
currents, and to provide an effective noise shield. The installation
of ready-access enclosures and the application of cable splicing
procedures as covered in RUS Standard PC-2, Bulletin 345-6
(proposed conversion to 7 CFR 1755.200), will usually ensure
adequate bonding of shields from a protection standpoint.
3.2.3 Bonding Cable Shields to Support
Strands (Messengers) : Cable shields should be bonded
to support strands (messengers) at frequent intervals to prevent
arcing and to provide a low impedance path to ground for power
contact or lightning related surge currents. Plastic-jacketed
cable should be bonded between the shield and strand at all
splices, terminals, and loading points. The methods of bonding
the shield to the strand depend on the types of enclosures
used and are described in detail in PC-2.
3.2.3.1 Four or more bonds per mile (Two and
one-half or more bonds per kilometer [km]) should be provided
if possible without opening the plastic jacket solely for
this purpose. Where long runs without splices, terminals,
or load points are involved, at least one bond per mile (1.6
km) should be provided even if the cable sheath has to be
opened solely for this purpose. If more than one cable is
attached to the same pole, the shields of the various cables
should be bonded together: (1) at crossing poles; (2) at the
beginning and ending of multi cable runs; and (3) at approximately
1500 foot (460 meter) intervals in long multi-cable runs.
3.2.4 Grounding of Cable Shields/Support
Strands (Messengers) : Normal construction practices
and NESC provisions require that cable shields, messengers,
and other non-current carrying metallic hardware be effectively
grounded. It is especially important to effectively ground
cable shields, messengers and non-current-carrying metallic
hardware at dead ends and other junction points for noise
mitigation, personnel protection, and/or power contact protection.
Such grounds are also beneficial in reducing lightning potentials
between the core and the shield if voltage limiting gaps (such
as terminal studs or arrester gaps) are applied to the conductors.
Grounds are also beneficial in reducing the probability of
fusing of cable conductors from lightning surges by diverting
a portion of the surge to ground before it reaches the cable
conductors. (See Section 4 of this bulletin for additional
detail on grounding provisions.)
3.2.5 Gas Tubes or the Equivalent
at Junctions with Facilities Serving Severely Exposed Stations
: At junctions with facilities of any type or length
serving stations that are severely exposed to lightning surges
(such as fire towers and radio towers), it is recommended
that 800 volt or greater breakdown gas tube arresters be installed
on the exposed pairs between the conductors and the shield.
An accepted alternative to gas tubes would be to install yellow-coded,
10 mil (0.3 mm) gap carbon arresters.
3.2.6 Protection Against Fusing of
Cable Conductors : The probability of fusing cable
conductors can be minimized by providing conducting paths
for surge currents, which divert the incoming surges to the
shield and ground before they reach the cable conductors.
The measures described in Paragraphs 3.2 through 3.2.5 usually
accomplish this.
3.2.7 Service Drops : Arresters
for lightning protection are not normally required at points
where service drops are connected along aerial cable runs.
Connections of drop wires to aerial cable conductors normally
should be made so as to meet National Electrical Code (NEC),
formally identified as ANSI/NFPA 70, fuse coordinating requirements
for station protection. Connection details are shown on the
Construction Drawings in the "Telephone System Construction
Contract," RUS Form 515.
3.2.8 Supplementary Measures :
In addition to the above items, under severe exposure conditions,
supplementary protection measures may be needed, e.g., plant
protection near electric power generating stations and substations.
Details of such supplementary protection should be determined
by a borrower after a careful study.
4. BONDING AND GROUNDING FOR POWER
CONTACT PROTECTION
4.1 Bonding at Power Crossings :
Where practicable, crossings between aerial telephone cables
and electric distribution lines of any type should be made
on jointly used or jointly occupied poles. At joint pole crossings
with Multi Grounded Neutral (MGN) type power lines, the cable
support strand (messenger) should be interconnected to the
MGN via a vertical pole ground wire. Where it is not practicable
to obtain joint pole crossings with electric distribution
lines and for all aerial crossings with electric transmission
lines, in span crossings may be used. For all in span crossings,
protection of the telephone plant depends primarily on adequate
structural strength and clearances, which in some cases may
require putting the telephone plant in underground conduit
or using buried cable.
4.2 Bonding in Joint Use or Joint
Occupancy :
4.2.1 Where a telephone cable is supported
by the same poles used for electric supply circuits of the
MGN type, the cable shield and suspension strand (messenger)
should be grounded by bonding the strand to the MGN as described
in Paragraph 4.2.4. These bonding connections should be made
at the following locations:
4.2.1.1 Where the joint use or joint occupancy
arrangement begins and ends;
4.2.1.2 On every electric supply pole that
carries a vertical pole ground wire to which are connected
transformers, capacitors or other types of power equipment
that draw load current under normal conditions; and
4.2.1.3 If the joint use or joint occupancy
section is longer than 1/2 mile (0.8 km), bonds should be
made to the MGN every 1/4 mile (0.4 km). The NESC requires
additional grounding considerations for certain messenger
sizes where the messengers are exposed to possible power contacts,
power induction, or lightning. If the ampacity of the messengers
are not adequate for system grounding conductors, grounding
of messengers has to be increased to intervals of eight per
mile (1.6 km).
4.2.2 Where telephone cables are supported
by the same poles used for electric supply circuits of the
non-MGN type, cable shields should be grounded by means of
their connections to the central office ground and by such
other additional grounds as necessary to satisfy the frequency
of occurrence described in Paragraph 4.2.1.3. Cable suspension
strand should be bonded to the vertical pole ground wire on
poles carrying vertical pole ground wires to which are connected
transformer, capacitors, or other types of equipment that
draw load currents.
4.2.3 Vertical pole ground wires on electric
supply poles interconnected to transformers or capacitor banks
should be connected directly to the power system neutral.
The transformers or capacitor banks should also have direct
connections to the power system neutral. At such locations
visual inspection from the ground should be made, before climbing,
to ascertain that the vertical pole ground wire is actually
connected to the neutral. If the vertical pole ground wire
is not connected, this fact should be reported to the power
company; and the wire should be regarded as energized. The
pole should not be touched or climbed by the telephone line
workers until the condition has been corrected by the power
company.
4.2.4 Where interconnection of the support
strand (messenger) to the MGN is recommended in 4.1 and 4.2.1,
the interconnection should be accomplished by the appropriate
method for the conditions prevailing at the pole in question
as listed below:
4.2.4.1 If the pole is already equipped with
vertical pole ground wire connected to the MGN, then a ground
wire assembly unit (PM2A) should be installed. A bonding conductor
should be attached to vertical ground wire by telephone construction
personnel if it is satisfactory to the power company.
4.2.4.2 If the pole is not equipped with vertical
ground wire, a ground wire assembly unit (PM2A) should be
installed and sufficient slack left to permit the bonding
wire to be extended to and connected to the MGN if the pole
in question is at the beginning or at the end of the joint
use section. Connection of the bonding wire to the MGN should
be made only by the power company. For intermediate bonds
recommended by 4.2.1, a pole already equipped with a pole
ground wire should be selected and a ground wire assembly
unit (PM2A) should be installed.
4.2.5 In most instances, interconnection of
the cable shield to the MGN will result in a decrease in noise
levels on the telephone system because of the additional shielding
effect provided by the neutral conductor. In a few instances
noise levels could increase if excessive residual power currents
flow in the shield as a result of bonding. This situation
is most likely to occur if the resistance of the neutral to
ground is relatively high. In such instances removal of a
number of bonds to the MGN to reduce the shield current usually
will be beneficial.
5. MISCELLANEOUS SITUATIONS
5.1 Underground/Buried Cable Dips
in Aerial Cable Runs : No special protection is
required at the junctions of aerial cable and short underground
or buried plastic-sheathed cable dips in aerial cable runs.
5.2 Protection at Loading Points :
Loading coils meeting RUS specification PE-26 are
designed such that no supplementary protection is required
in addition to the measures recommended herein for protection
of the associated cable.
5.3 Buffer Protection :
Where a good shield ground such as a MGN of approximately
25 ohms or less cannot be obtained at or within 200 feet (60
meters) of a cable-noncable junction, the beneficial effect
of such a ground may be achieved by placing buffer protection
in the form of yellow coded arresters between the non-cable
pairs and ground at a point about 1500 feet ± 1000
feet (460 meters ± 300 meters) from the junction, provided
a ground of approximately 25 ohms or less can be obtained
at that point .
5.4 Pole Lightning Protection Wires
: Lightning protection wires may be necessary to
prevent the splitting of wood poles used for cable supports
in certain areas of high lightning incidence and severe exposures.
RUS borrowers should make a study of local conditions to determine
to what extent this protection is required. Normally, extensive
use of lightning protection wires is necessary in the shaded
areas of the map on Figure 1, Lightning Damage Probability
Map , and in unshaded areas which have more than 60 thunderstorm
days per year. In systems within areas affected by high levels
of lightning damage and where local experience clearly indicates
the need, lightning protection wires should be installed on
poles which are severely exposed because of being on or near
the top of a hill with little or no shielding such as buildings,
trees, or a higher foreign pole line. In hilly areas, installation
of protection wires on a number of consecutive poles is desirable.
With flat terrain where the exposure is more uniform and less
severe, protection wires should be installed on every third
or fourth pole. In the unshaded areas of the map in Figure
1, which have less than 30 thunderstorm days per year, pole
lightning wires are not necessary. (Note: RUS Borrower areas
not shown on Figure 1, such as Alaska, Hawaii, and the Federated
States of Micronesia, Guam, Puerto Rico, Republic of Marshall
Islands, Republic of Palau, and the Virgin Islands are considered
low probability lightning damage areas.)
6. ELECTRICAL PROTECTION FOR BURIED/UNDERGROUND
CABLE
6.1 Plastic-Insulated Conductor (PIC) Cable
and Wire : Polyethylene insulated conductor
and jacketed cable and wire require a minimal of electrical
protection because of their inherent high dielectric strength
and quality. Difficulties caused by dielectric failure have
been reduced to a minimal amount through the extensive application
of PIC cable and wire. Power cross, lightning surge, and other
sources of unwanted high currents on the telephone plant can,
at times, cause cable or wire conductors to fuse. While finer
gauge conductors are more susceptible to this type of damage,
the economic advantage in their use will usually outweigh
the higher rate of fusing incidence as compared with coarser
gauge facilities.
6.2 Lightning Protection : Buried cable and
wire are not normally as susceptible to damage from lightning
surges as other categories of outside plant. However, buried
plant may be subjected to lightning damage in one of the following
ways: (1) by direct strokes to the shield or strokes-to-ground
which are eventually directed to the shield; (2) by surges
conducted to the buried plant from connecting facilities which
are struck; (3) by induction from nearby strokes-to-ground;
and (4) by currents developed because of a rise in ground
potential at stroke points near grounded station protectors
or other grounded facilities. While the dielectric strength
of PIC cable will withstand most of the surges occurring from
items 2, 3, and 4 above; direct lightning strokes will normally
cause damage to the cable. The damage is caused by the magnitude
of currents involved. However, direct strokes to buried cable
occur infrequently.
6.2.1 Current surges which reach buried and
underground cables from conductors of connecting plant such
as buried line wires, buried services, or aerial non-cable
type plant, are usually confined to the conductors by the
high dielectric strength of the plastic insulation on the
conductors and the inner jacket. Frequently the exposed connecting
conductors have a coarser gauge than the buried cable conductors
to which they connect. Both the coarser gauge of connecting
conductors and the high dielectric strength of the plastic
insulations tend to increase the probability of fusing the
cable conductors.
6.2.2 The use of buried fine gauge cable conductors
in telephone systems has resulted in conductor fusing becoming
more prevalent than dielectric failure.
6.2.3 As noted previously, loading coils meeting
RUS specification PE-26, are designed to withstand substantial
lightning surges without damage. Present designs will withstand
current surges which approach the fusing current of 28 AWG
wire. While this fusing current is less than that of 24 AWG
cable, it is large enough that only a small percentage of
surges reaching cables will cause loading coil damage. Therefore,
gap protection of loading coils in buried plant is not normally
required. In areas susceptible to very severe lightning damage,
protection for loading coils can be added at a later date
if needed. Where protection of loading coils is necessary,
standard or heavy duty gas tubes with a slowly rising dc breakdown
voltage of approximately 350 Volts should be used. It is recommended
that these gas tubes be connected in a longitudinal non-grounded
bypass tube configuration, as discussed in TE&CM Section
822, "Electrical Protection of Carrier Equipment", (proposed
conversion to Bulletin 1751F-822).
6.3 Power Contact Protection :
Cable and wire facilities which are actually buried in the
earth are not considered as being exposed to power line contacts
except those buried in the same trench with power distribution
cables. Protective measures are, therefore, not required for
buried plant except for those which may be required for the
protection of connecting facilities, subscriber stations,
and exposed aerial inserts as prescribed in practices covering
such plant and as supplemented herein. Aerial inserts in buried
plant are considered as being exposed when the possibility
exists that they could be contacted by power line conductors
operating in excess of 300 volts to ground. Where joint buried
construction is involved, protection measures should be applied
as described in TE&CM Section 640, "Design of Buried Plant-Physical
Considerations", (proposed conversion to Bulletin 1751F-640).
7. LIGHTNING PROTECTION FOR BURIED/UNDERGROUND
PLANT
7.1 Dielectric Protection of Buried/Underground
Plant is limited to the following measures: (1)
gas tube or equivalent arresters at junctions with facilities
serving severely exposed stations and (2) bonding and grounding
of buried wire and cable shields.
7.2 Facilities Serving Severely Exposed
Stations : Terminal blocks equipped with standard
or heavy duty gas tube arresters having dc breakdown voltages
of 800 volts or greater and installed in suitable mountings
and enclosures are recommended at junctions between buried
wire or cable and facilities serving stations that are severely
exposed to lightning (such as fire towers and radio towers)
regardless of the length or type of connecting facilities.
Yellow coded (10 mil) (0.3 mm) carbon blocks may be used as
an alternative to gas tubes.
7.3 Bonding/Grounding of Buried Wire
and Cable Shields :
7.3.1 Complete bonding of shields of buried
cable and wire to maintain electrical continuity of shields
throughout the buried plant and the connections from buried
plant to aerial plant, central offices, and subscriber station
protectors is recommended. Grounding of buried cable and wire
shields is advantageous from lightning protection considerations
and is a requirement of the NESC (to effectively ground non-current
carrying metallic plant).
7.3.2 The shields of all buried wires and
cables entering a central office should be bonded to each
other and interconnected with the central office ground bus
or grounding conductor. This bonding eliminates harmful differences
of potential between the various cables entering the central
office. RUS requires special bonding and grounding at central
offices. See Paragraph 3.2.1 of this bulletin for some of
the basic considerations of the special grounding and bonding
that RUS requires at central offices. For more specific details,
see TE&CM Section 810 (proposed conversion to RUS Bulletin
1751F-810).
7.3.3 At junction points the shields and support
wires of interconnecting facilities should be bonded to the
metallic shield of the main buried cable or wire. The grounding
bracket in terminal housings should be used to facilitate
making these connections. The grounding bracket should be
connected to a ground rod with at least a #6 AWG grounding
conductor. The shield of buried service wires should likewise
be bonded to the metallic shield of the main cable and connected
at the subscriber end to the station protector grounding terminal.
7.3.4 The use of pulse code modulation (PCM)
carrier systems and the concern for near end crosstalk (NEXT)
has led to the development of a cable in which the pairs are
divided into two bundles which are isolated from each other
by a "screen" designed to reduce the crosstalk from one bundle
to the other primarily by reducing the capacitance unbalance
between pairs. Because this screen does not have the same
insulation as the cable shield, the screen should not be treated
as a shield where electrical protection is concerned. The
screen should not be connected to ground at any point and
it should deliberately be made electrically discontinuous
at pedestals.
7.4 Protection of connecting facilities having
appreciably lower dielectric strength than plastic-insulated
conductor (PIC) cable and wire is required as follows: (1)
arresters at the central office, and (2) arresters at carrier
repeaters and terminals.
7.4.1 Arresters at the central office provide
main frame arrester protection on all cable pairs entering
the central office.
7.4.2 Carrier repeaters and terminals and
most other electronic equipment used on cable pairs have low
dielectric strength compared with the dielectric strength
of cable pairs. Such equipment should, therefore, be protected
in accordance with RUS TE&CM Section 822 (proposed conversion
to RUS Bulletin 1751F-822).
8. POWER CONTACT PROTECTION FOR BURIED/UNDERGROUND
PLANT
8.1 Aerial Inserts : Aerial
inserts may consist of strand supported buried cable, underground
cable, aerial cable, or wire supported buried wire. When an
aerial insert of any type is exposed to power contacts by
being joint with, crossing under, or otherwise subject to
possible contact with power conductors operating at voltages
in excess of 300 volts, the aerial insert should be considered
as exposed. Support strands (messengers) or wires of exposed
aerial inserts should be effectively grounded by connecting
to an MGN. If an MGN is not available, effective grounding
by driven electrodes or other means is necessary. The support
strand (messenger) of aerial inserts should be grounded in
accordance with the NESC at four or eight times a mile (1.6
km), depending on the conductivity of the support strand (messenger).
(See Rule 215C3 of the NESC and Paragraph 4.2.1.3 for details).
Because RUS has standardized on use of #6 AWG copper grounding
conductors, seven wire steel strand messengers of 1/4" (6.4
mm) and 5/16" (7.9 mm) should be grounded 8 times each mile
(1.6 km) while 3/8" (9.5 mm) and 7/16" (11 mm) should be grounded
four times each mile (1.6 km).
8.1.1 The conductors of exposed aerial inserts
in buried wire or cable should be isolated from the buried
portions on both sides of the insert in order to maintain
the unexposed status of the buried plant. Isolation of the
conductors of exposed aerial inserts is necessary so that
fuseless-type station protectors may be used and isolation
may be accomplished by any of the following procedures:
8.1.1.1 If the conductors of the buried plant
on both sides of the aerial insert are 24 AWG copper or smaller,
no fuse links are required . Buried type wire or cable may
be used for the aerial insert following construction practices
for aerial cable.
8.1.1.2 If the conductors of the buried plant
are coarser than 24 AWG copper, the preferred construction
is to install 24 AWG cable as the aerial insert. The 24 AWG
insert then provides the necessary fusing coordination with
the connected stations on both sides of this insert. Where
the aerial insert extends for more than a few spans, the effect
of the use of 24 AWG on transmission should be checked.
8.1.1.3 If the conductors of both the buried
plant and the aerial insert are coarser than 24 AWG, isolation
of the exposed aerial insert should be accomplished by providing
24 AWG copper fuse links between the aerial insert and the
buried portions of the cable. These fuse links should be applied
at both ends of the exposed insert, as shown in Drawings 951
and 952 of RUS Bulletin 345-150, RUS Form 515a. In order to
minimize the cost of isolating aerial inserts, the 24 AWG
links should usually be installed in terminal housings that
are required for other purposes at points nearest to each
end of the aerial insert. Color-coded 24 AWG leads at least
8 inches (20.32 centimeters) long should be spliced in series
with each conductor of the cable between the end of the buried
portion of the cable and the adjoining end of the aerial insert.
The color code should be preserved. If subscriber's services
or buried wire branch tap leads are distributed from the buried
plant terminal housings involved, the leads should be connected
to the unexposed side of the fuse link. Exposed aerial taps
should be connected to the exposed side of the fuse links.
The shields of all cables or wires in the buried plant terminal
housings should be bonded together and grounded to the same
ground electrode to which the support strand (messenger) is
grounded. A typical exposed aerial insert is shown in Drawing
951 of RUS Bulletin 345-150.
8.2 Aerial Line Extensions :
All aerial noncable-type line extensions from buried plant
should be connected to the buried wire or cable through a
wire link capable of safely fusing at currents less than the
ampacity (current carrying capacity in amperes) of the subscriber's
service. The 24 AWG copper leads connected to terminal blocks
or 20 AWG bridle wires are adequate for this purpose. The
term "noncable-type circuits" as used here refers to wire
circuit facilities not enclosed in a metallic shield. Buried
wire is considered to be a "cable type" facility.
8.2.1 Where buried plant facilities are extended
by exposed aerial wire facilities, power contact protection
should be applied to the aerial facilities in accordance with
applicable RUS practices. Where the applicable practices require
protection devices at the junction with buried plant, the
low impedance ground required for the power protection device
should be utilized to provide additional lightning protection
to the buried plant. A low impedance path to ground can be
accomplished by bonding the buried cable or wire shield to
the grounding conductor or ground electrode of the power contact
protector.
8.3 Aerial Drop Wires Connected to
Buried Plant : Where economically feasible, the connection
of aerial drop wires to buried wire or cable should be avoided
in favor of buried services.
8.3.1 Aerial drop wires exposed to the possibility
of contact with electric distribution facilities operating
in excess of 300 volts to ground should be connected to the
buried facilities through a 24 AWG copper fuse link or a 20
AWG. This fuse link is recommended as a protective measure
to prevent large fault currents from reaching other stations
served by the buried wire or cable. It will also prevent damage
to coarser gauge buried facilities. The station being served
should be protected in accordance with applicable station
protection practices.
9. GROUNDING OF BURIED WIRE AND CABLE
SHIELDS
9.1 Grounding at Junctions :
As previously indicated, grounding of buried wire or cable
shields at junctions with other types of facilities is recommended
by RUS and it helps in compliance with the NESC requirements
to effectively ground non-current carrying metal facilities.
10. METALLIC HOUSINGS ON VERTICAL
POWER POLES
10.1 Bonding : When a metallic
buried plant housing is mounted on a power pole, the grounding
conductor of the housing should be bonded with at least a
#6,AWG bare copper wire to the vertical pole ground wire,
if present, on the pole. The purpose of this bond is to maintain
the ground wire and the buried plant housing at the same potential,
thereby preventing a shock hazard that otherwise might exist
during a fault condition on the power line.
10.2 When Carrier Equipment is not
Grounded : With certain types of cable carriers,
the carrier equipment manufacturers have recommended that
the carrier equipment not be connected to an electric system
ground. In such instances carrier equipment housings and/or
metallic buried plant housings enclosing carrier equipment
should be bonded to vertical pole ground wires as recommended
in Paragraph 10.1, but the carrier circuitry and chassis should
be isolated from the metallic housing by insulation having
at least 20 kV dc dielectric strength. The provision of this
dielectric between the carrier circuitry and the housing makes
it possible to use floating by-pass protection or protection
grounded to a remote separate ground, and still maintain the
buried housing at the same potential as the vertical pole
ground wire. It is the responsibility of the carrier equipment
suppliers to provide the 20 kV dielectric strength between
the carrier circuitry and chassis, and the metallic housing.
See TE&CM Section 822 (proposed conversion to RUS Bulletin
1751F-822) for additional details on carrier protection.
11. EFFECTIVE GROUNDING OF CABLE SHIELDS
11.1 General : Application
of an effective grounding system is recommended for all locations.
Both the National Electrical Code (NEC) and the National Electrical
Safety Code (NESC) cite a 25 ohm resistance-to-ground for
grounding systems. See Section 250-84 of the NEC and Rule
96B of the NESC. Note by attempting to obtain at least four
grounds per mile (1.6 km), attention to obtaining 25 ohms
at individual grounds is not necessary (except at special
equipment sites) as the multiplicity of grounds helps to achieve
an overall low impedance to ground.
11.2 The Purpose of Grounding Cable
Shields is to protect telephone plant from the effects
of ground potential rise (GPR) caused by power system faults.
Grounding telephone cable shields helps to direct excessive
voltages and currents induced on the shields to earth. This
can often be achieved before these currents and voltages reach
the location of plant or equipment requiring protection.
11.3 The Application of an Effective
Grounding System can increase the flow of current
in the shielding circuit and help to reduce noise. The shield
should be continuous with no opens or bonding problems, so
that the maximum benefits of effective grounding can be realized.
11.4 Isolating Damage Caused by a
Lightning Stroke : An effective grounding system
can isolate damage by dissipating the current through multiple
paths to ground along the cable shield. Because of the high
magnitude of current in a lightning strike and the associated
GPR, it is not feasible to protect the entire telephone plant
from damage. As a result it is desirable to isolate damage
from a near or direct lightning strike to the least plant
length as possible.
11.5 Obtaining a 25 Ohm Ground
Provision of a ground at every location with a resistance-to-ground
of 25 ohms or less cannot always be accomplished with a 5
foot (1.5 meter) ground rod. Use of a longer rod or multiple
rods connected together may be necessary. This is especially
true in areas of the country where there is an extremely high
earth resistivity. In many areas of the country the winter
frost line exceeds 18 inches (45.7 cm) or more. In such areas
of the country use of eight foot (2.4 meter) rods should be
made standard practice.
12. EFFECTIVE GROUNDING THEORY
12.1 Effective Grounding
is based on the theory that multiple grounds along a cable
shield will provide a low resistance-to-ground. This low resistance-to-ground
provides for the dissipation of high voltages and currents
induced or conducted on the cable shield.
12.2 Spacing of Electrodes :
For protection purposes, it is desirable to have the earth
electrodes spaced every quarter mile (0.4 km) but this is
not practical in most buried cable plant. In aerial plant,
especially in situations of joint use or joint occupancy,
grounding of messengers at four or eight times a mile (1.6
km) is required by the NESC and is most beneficial because
the lower the value of effective resistance-to-ground, the
better the overall system will perform during power cross
situations.
12.3 Selection of Electrode :
Once the earth resistivity at a location has been determined,
selection of the proper electrode can be made. A 5 foot (1.5
meter) rod is normally used. If the earth resistivity at the
location is extremely high, an 8 foot (2.4 meter) rod should
be used. An 8 foot (2.4 meter) rod should also be used in
areas where the average frost line is 18 inches (45.7 cm)
or deeper.
CLICK
HERE FOR PRINTABLE VERSION
|