| Outside
Plant Corrosion Consideration
UNITED STATES DEPARTMENT OF
AGRICULTURE
Rural Electrification Administration
BULLETIN 1751F-670
SUBJECT: Outside Plant Corrosion Considerations
TO: All Telephone Borrowers
REA Telephone Staff
EFFECTIVE DATE: Date of Approval
EXPIRATION DATE: Seven years from effective
date
OFFICE OF PRIMARY INTEREST: Outside Plant
Branch, Telecommunications Standards Division
PREVIOUS INSTRUCTIONS: This bulletin replaces
REA Telecommunications Engineering & Construction Manual
(TE&CM) 670, Corrosion Considerations in Telecommunications
in Outside Plant, Issue 2, dated January 1982.
FILING INSTRUCTIONS: Discard REA Telecommunications
Engineering & Construction Manual (TE&CM) 670, Corrosion
Considerations in Telecommunications in Outside Plant, Issue
2, dated January 1982, and replace it with this bulletin.
File with 7 CFR 1751 and on REANET.
PURPOSE: This bulletin provides REA borrowers,
consulting engineers, contractors and other interested parties
with information concerning the various aspects of corrosion
which should be considered in the preparation of a system
design.
Blaine D. Stockton, Jr. 09/02/93
______________________________ __________________________
Administrator Date
TABLE OF CONTENTS
1. General . . . . . . . . . . . . . . . .
. . . . . . . . . 6
2. Corrosion Theory . . . . . . . . . . .
. . . . . . . . . 6
3. Types of Corrosion . . . . . . . . . .
. . . . . . . . . 8
4. Corrosion Behavior of Metals Used in Outside
Plant
Construction . . . . . . . . . . . . . . .
. . . . . . . 15
5. Corrosion Prevention Measures . . . . .
. . . . . . . . 19
6. Environmental Conditions Affecting the
Selection of
Cable or Wire Shields . . . . . . . . . .
. . . . . . . 23
7. Soil Measurements . . . . . . . . . . .
. . . . . . . . 27
TABLES & FIGURES
Table 1 Galvanic Series of Metals in Sea Water
. . . . . 10
Table 2 Soil Corrosivity Versus Resistivity
. . . . . . . 27
Table 3 Typical Soil Resistivity Values .
. . . . . . . . 28
Figure 1 Example of Galvanic Corrosion . .
. . . . . . . . 30
Figure 2 Example of Concentration Cell Corrosion
. . . . . 31
Figure 3 Example of Stray Current Corrosion
. . . . . . . 32
Figure 4 Anchor Rod Corrosion - Galvanic Couple
. . . . . 33
Figure 5 Anchor Rod Corrosion - Differential
Aeration Cell 34
Figure 6 Coordinated Stray Current Protection
. . . . . . 35
Figure 7 Estimated Average Earth Resistivity
Northeast Region . . . . . . . . . . . . .
. . . 36
Figure 8 Estimated Average Earth Resistivity
Southeast Region . . . . . . . . . . . . .
. . . 37
Figure 9 Estimated Average Earth Resistivity
North Central Region . . . . . . . . . . .
. . . 38
Figure 10 Estimated Average Earth Resistivity
Western Region . . . . . . . . . . . . . .
. . . 39
Figure 11 Estimated Average Earth Resistivity
Southwest Region . . . . . . . . . . . . .
. . . 40
Figure 12 Soil Resistivity Measurement Procedure
. . . . . 41
INDEX:
Outside Plant
Corrosion
Telecommunications
ABBREVIATIONS
ASTM American Society For Testing And Materials
AWG American Wire Gauge
B Distance between electrodes
cm Centimeter
cm/m Centimeter per meter
dc Direct current
EMF Electromotive Force
m Meter
NOx Nitrogen oxides
ohm·cm Ohm·centimeter
OH- Hydroxyl ion
P Average earth resistivity
pH Potential of hydrogen
R Resistance
REA Rural Electrification Administration
SOx Sulfur oxides
TE&CM Telecommunications Engineering and
Construction Manual
Ð Greek Letter, Pi, = 3.1416
DEFINITIONS
Active: A state in which a metal tends to
corrode (opposite of passive). In a corrosion cell the active
or corroding metal is the metal which is more negative in
potential.
Amphoteric Metal: A metal susceptible to corrosion
in both acidic or alkaline environments.
Anode: The electrode of an electrolytic cell
at which oxidation or corrosion occurs (opposite of cathode).
(Electrons flow away from the anode in the external circuit.
It is usually the electrode where corrosion occurs and metal
ions enter solution.)
Cathode: The electrode of an electrolytic
cell at which reduction (and practically no corrosion) occurs
(opposite of anode). (Electrons flow toward the cathode in
the external circuit.)
Cathodic Polarization: Polarization of the
cathode; a reduction from the initial potential resulting
from current flow effects at or near the cathode surface.
Potential becomes more active (negative) because of cathodic
polarization.
Cathodic Protection: Reduction or elimination
of corrosion by making the metal a cathode by means of an
impressed direct current or attachment to a sacrificial anode.
Concentration Cell: A cell involving an electrolyte
and two identical electrodes, with the potential resulting
from differences in the chemistry of the environments adjacent
to the two electrodes.
Differential Aeration Cell: A concentration
cell caused by differences in oxygen concentration along the
surface of a metal in an electrolyte.
Electrolyte: A substance that dissociates
into ions in solution or when fused, thereby becoming electrically
conducting.
Electromotive Force Series: A list of elements
arranged according to their standard electrode potentials
within an electrolyte, with noble metals such as gold being
positive and active metals such as zinc being negative.
Galvanic Cell: A cell consisting of two dissimilar
metals in contact with each other and with a common electrolyte
(sometimes refers to two similar metals in contact with each
other but with dissimilar electrolytes; differences can be
small and more specifically defined as a concentration cell).
Galvanic Corrosion: Corrosion associated with
the current resulting from the electrical coupling of dissimilar
electrodes in an electrolyte.
Galvanic Series: A list of metals and alloys
arranged according to their relative corrosion potentials
in a given environment.
Holiday: A discontinuity (hole or gap) in
a protective coating.
Local Cell: An electrochemical cell created
on a metal surface because of a difference in potential between
adjacent areas on that surface.
Monel: A corrosion-resistant alloy of nickel,
copper, iron, and manganese.
Noble: The positive (increasingly oxidizing)
direction of electrode potential.
Oxidation: Loss of electrons by a constituent
of a chemical reaction. (Also refers to the corrosion of a
metal that is exposed to an oxidizing gas at elevated temperatures.)
pH: A measure of the acidity or alkalinity
of a solution, numerically equal to 7 for neutral solutions,
increasing with alkalinity and decreasing with increasing
acidity.
Passive: The state of the metal surface characterized
by low corrosion rates in a potential region that is strongly
oxidizing for the metal.
Pitting: Corrosion of a metal surface, confined
to a point or small area, that takes the form of cavities.
Polarization: The change from the open-circuit
electrode potential as the result of the passage of current.
Reduction: The gain of electrons by a constituent
of a chemical reaction.
Stray Current Corrosion: The corrosion caused
by electric current from a source external to the intended
electrical circuit, for example, extraneous current in the
earth.
Stress Corrosion Cracking: A cracking process
that requires the simultaneous action of a corrodent and sustained
tensile stress. (This excludes corrosion-reduced sections
which fail by fast fracture. It also excludes intercrystalline
or transcrystalline corrosion which can disintegrate an alloy
without either applied or residual stress.)
1. GENERAL
1.1 Corrosion of metals is one of the many
problems that has to be considered by engineers when designing
aerial, direct buried, or underground telecommunications systems.
If not controlled, corrosion can result in costly replacement
of facilities. The information and recommendations in this
bulletin are advisory.
1.2 The Rural Electrification Administration
(REA) Tele-communications Engineering and Construction Manual
(TE&CM) 218, Plant Annual Cost Data for System Design
Purposes (Planned conversion to REA Bulletin 1751B-230), provides
cost data showing the depreciation rates and maintenance expenses
to be applied to the various plant items in different areas
throughout the United States. However, in some locations,
corrosive conditions may exist which can greatly increase
maintenance expense and cause the early replacement of some
plant items. This can result in a severe economic burden on
the operating telecommunications company.
1.3 Corrosive atmospheric conditions may exist
over an entire service area of a telecommunications system,
or may be confined to relatively small areas within the total
service area. Rural environments which are usually free from
industrial contaminants, represent most of the total land
area of the United States. Exposed metals are expected to
provide a relatively long service life when installed in rural
areas. For example, galvanized steel has long been used in
the telecommunications and electric power utilities and to
learn of conductors and strand still in use after 40 years
of service is not uncommon. The life expectancy of galvanized
steel will vary with the amounts of contaminants present in
the atmosphere. In severely corrosive environments, Class
A galvanized coatings on steel conductors and strand may last
for as little as 3 years.
1.4 The processes of corrosion are not always
simple and their effects are not easily predicted. In many
cases the effects of one type of corrosion will mask the effects
of another type of corrosion so that neither is recognized.
The following sections discuss the theory of corrosion and
the application of this theory to practical situations in
telecommunications systems.
1.5 A comprehensive set of definitions of
terms relating to corrosion can be found in American Society
For Testing And Materials (ASTM) G 15, Standard Terminology
Relating to Corrosion and Corrosion Testing.
2. CORROSION THEORY
2.1 Corrosion may follow any one of several
general patterns. Basically stated, corrosion results from
the instability of a construction material with the environment
in which the material is placed. All materials, both organic
and inorganic, can react with their environments and may eventually
lose their usefulness for a given application. Some nonmetals
tend to decompose, usually as the result of chemical interaction
with some component of their environment.
2.2 Corrosion is the result of electrochemical,
chemical, or biological reaction between a metal and its surroundings.
Many of the destructive effects of corrosion are due to electrochemical
reaction. The basic requirements for corrosion to occur in
a given corrosion cell are as follows:
a. An anode and cathode must be present to
form a cell;
b. An electrically conducting medium (electrolyte)
contacting both the anode and cathode must
be present;
c. A metallic connection between the anode
and cathode
must be present; and
d. A direct current (dc) potential between
the anode and
cathode causing current to flow must be present.
2.2.1 The anode is that metallic part of a
corrosion cell from which metal ions separate from the metal
and flow into the surrounding electrolyte. The metal is consumed
(corroded) at the anode by this action. The cathode is that
metallic part of a corrosion cell to which positively charged
ions in the electrolyte flow and react with the negatively
charged electrons in the metal. The cathode metal in an individual
corrosion cell does not normally corrode, except when amphoteric
metals are involved. Amphoteric metals are metals that corrode
in either acidic or alkaline environments. If such metals
are made excessively cathodic, the chemical reaction at the
cathode can make the environment extremely alkaline and can
cause corrosion to occur. Aluminum and lead are examples of
amphoteric metals.
2.2.2 The anodes and cathodes can be adjacent
(local cells) or far apart. The current can be self-generated
or it can be impressed on the system from an outside source.
The conducting medium can be water, wet soil or any solution
which conducts electricity.
2.3 The anode corrodes. Metal at the anode
chemically reacts with the electrolyte causing minute pieces
of metal to dissolve and flow into the electrolyte. In the
process the minute pieces of metal lose negatively charged
electrons to the anode metal and the minute pieces of metal
enter into the electrolyte as positively charged ions. The
loss of electrons by the metal ion at the anode is referred
to as oxidation. The excess electrons left by the metal ions
at the anode flow through the metal or through an external
metallic path to the cathode. At the cathode-electrolyte interface
electrons leave the metal and chemically react with positively
charged ions in the electrolyte. The electron gain by the
positively charged ions in the electrolyte at the cathode
is referred to as reduction.
2.3.1 Since the generally accepted concept
for the flow of electric current is opposite to the direction
of electron flow, current flow in a corrosion cell is from
anode to cathode in the electrolyte and from cathode to anode
in the metal or metallic path.
2.3.2 The quantity of metal lost by the corrosion
process is directly proportional to the amount of direct current
which flows through the corrosion cell and early in the 19th
century was quantitatively shown by Michael Faraday to be
in accordance with the following equation:
W = k * I * t
Where:
W = Weight Loss in grams
k = Electrochemical Equivalent in grams/coulombs
I = Current in amperes
t = Time in seconds
It can be seen that for a given amount of
current over a given period of time, the electrochemical equivalent
(k) is the variable which determines the actual weight loss
of the metal or material. Each metal or material has its own
electrochemical equivalent which is a natural characteristic
of that metal or material. For example, one ampere of current
flowing for one year will corrode about 9 kilograms of steel.
2.4 When the positive metal ions leave the
metal anode (corrosion sites), the remaining electrons flow
to cathodic sites where they are discharged during the cathodic
reactions. The principal cathodic reactions include hydrogen
ion reduction to form hydrogen gas, oxygen reduction to form
hydroxyl ions (OH-), and reduction of water to hydroxide ions.
Cathodic polarization occurs when the reaction products cover
the cathodic sites. The rate of corrosion in soils is often
controlled by the rate at which the reactants are supplied
to, or the reaction products are removed from the cathodic
sites (cathodic depolarization). Similarly, polarization may
occur at the anode due to concentration of metal ions although
this phenomena is of lesser importance in the soil. In the
presence of moisture, the metal ions react with hydroxide
ions to form hydroxides which in turn react with oxygen to
form oxides thus producing both cathodic and anodic depolarization.
3. TYPES OF CORROSION
3.1 Galvanic Corrosion
3.1.1 The corrosion resulting from current
generated from differences in potential of metals in an electrolyte
is referred to as galvanic corrosion.
3.1.2 Dissimilar metals, coupled electrically
and placed in a conductive solution, satisfy the requirements
for the basic corrosion cell. Two electrically coupled metals,
in the presence of an electrolyte, constitute a special corrosion
cell, called a galvanic cell, wherein one of the metals becomes
cathodic and the other becomes anodic and corrodes. If the
potential difference between the metals is small, corrosion
usually will be slow. Conversely, if the potential difference
between the metals is large, corrosion will usually be rapid.
3.1.3 During the galvanic corrosion process,
an electric current flows as a result of the difference in
the electrode potential of the two metals coupled electrically.
The magnitude of the current determines the degree of corrosion
of the more vulnerable material over and above the material's
natural rate of deterioration alone in the same electrolyte.
The quantity of galvanic corrosion is defined as the corrosion
resulting from the electrochemical reaction. In the past galvanic
has been erroneously defined as the total corrosion including
normal decomposition.
3.1.4 An example of Galvanic Corrosion is
shown in Figure 1. The galvanized steel 3-bolt clamp and the
galvanized steel anchor rod act as anodes and the copper-steel
guy strand acts as the cathode. The corrosion of the anchor
rod and the 3-bolt clamp will be increased over the normal
rate of corrosion by galvanic effect, unless the hardware
is provided with some coating to prevent air and moisture
from penetrating to the dissimilar metal connection.
3.1.5 From the galvanic corrosion behavior
of metals and alloys, metals can be arranged in a series which
will indicate their general tendency to form galvanic cells.
Such a series can be used to predict the probable direction
and the extent of galvanic effects. Table 1 is such a galvanic
series and includes most metals used in outside plant environments.
The table is qualitative and is intended only to indicate
trends. The arrangement of the metals in the series is based
on actual corrosion testing experience within sea water. Since
more observations of galvanic behavior have been made in sea
water than in any other single environment, the galvanic series
listed in Table 1 should be used as a first approximation
of the probable direction and extent of the galvanic effects
in other environments in the absence of data more directly
applicable to such environments. The only way of predicting
the direction and extent of the galvanic effects on a material
in a specific environment is to perform potential measurements
in the specific environment. The galvanic series listed in
Table 1 should not be confused with the Electromotive Force
(EMF) Series. In the EMF series the metals are arranged according
to the potentials developed when immersed in a solution of
their own ions of prescribed composition as to strength and
chemical nature. The EMF series is of theoretical value and
cannot be relied upon to predict the potential differences
between metals in outside plant operating conditions.
TABLE 1
Galvanic Series of Metals in Sea Water
ANODIC END (Most Active)
Magnesium
Magnesium Alloys
Zinc
Aluminum
Cadmium
Steel or Iron
Cast Iron
18:8 Stainless Steel (active)
18:8:3 Stainless Steel (active)
Lead-Tin Solders
Lead
Tin
Nickel (active)
Inconel (active)
Hastelloy (active)
Brass
Copper
Bronze
Copper:Nickel Alloys
Monel
Silver Solder
Nickel (passive)
Inconel (passive)
18:8 Stainless Steel (passive)
18:8:3 Stainless Steel (passive)
Hastelloy C (passive)
Silver
Graphite
Gold
Platinum
CATHODIC END (Least Active)
3.1.6 Some of the metals in Table 1 are grouped
together to indicate that the grouped members have little
tendency to produce galvanic corrosion on each other and,
therefore, are relatively safe to use in contact with one
another. However, the coupling of metals widely separated
in the series can result in galvanic corrosion of the metal
higher in the list, i.e., the one most anodic. Usually the
farther apart the two metals are in the series the greater
the corrosive tendency. The relative position of a metal within
a group sometimes changes with the environment, but rarely
does a metal change from group to group. Note that stainless
steel alloys 18:8 and 18:8:3 appear in two places in Table
1. They frequently change positions as indicated in the table
depending upon the corrosiveness of the sea water. These two
alloys demonstrate relatively good resistance to corrosion
in their passive, more noble, condition.
3.1.7 The surface areas of the metals forming
a galvanic cell are a major consideration in the rate of corrosion.
A small piece of aluminum coupled with a large piece of copper
will corrode much faster than a piece of aluminum equal in
area to the copper. If circumstances dictate that dissimilar
metals be in contact with one another, the area of the active
(anodic) metal should be large with respect to the area of
the passive (cathodic) metal.
3.2 Concentration Cell Corrosion
3.2.1 Another source of corrosion is ion concentration
variance within an electrolyte surrounding a single piece
of metal. Usually this form of corrosion originates in or
around crevices. Early detection and prevention depend largely
upon knowledge of the corrosion mechanism.
3.2.2 In general, the lower the metal ion
concentration, the greater the tendency of the metal to dissolve,
i.e., the lower the metal ion concentration, the higher is
its solution potential. When a single metal surface is exposed
to a corrosive environment which is not uniform in its metallic
salt concentration from point to point, corrosion results
in areas of lower concentration. Differences in oxygen concentration
at a metal surface within a solution also develop different
potentials over the points of contact with metallic surfaces.
In both cases, the zone of greatest attack will be in the
area of the more dilute ion or oxygen concentration. This
explains the rapid metal destruction associated with lap joints,
crevices, or deposits that interfere with the flow of electrolyte
over the entire surface of the metal.
3.2.3 As mentioned in Paragraph 3.2.2, differences
in oxygen concentration on a metal surface will cause voltage
differences to arise and thus accelerate the rate of corrosive
attack. These oxygen concentration cells are typically associated
with crevices or deposits that hinder diffusion of oxygen
into the solution under the deposit. The lower concentration
of oxygen creates an anode fostering corrosion which can eventually
weaken the structure. With some alloys the effect of the oxygen
concentration cell is exacerbated by electrolytic cells formed
between the relatively small areas of activated alloy (anode)
within crevices and large areas of passive alloy (cathode)
around crevices. These cells are similar to, but generally
more destructive than, normal oxygen concentration cells because
corrosion activity is concentrated in small areas. This type
of corrosion is most likely to be found in aluminum and stainless
steel, although any metal which has been treated to form a
protective coating may also be affected because of the possibility
for holidays or aberrations in the coatings where corrosion
may concentrate.
3.2.4 The concentration cell corrosion depicted
in Figure 2 shows one cause for failure of corrosion-resistant
steel (stainless steel) cable suspension strand in industrial
and marine atmospheres. Dirt and soot from an industrial area
or salt deposits in a marine atmosphere can settle upon the
surface, enter into the interstices of the strand and retain
moisture. A differential aeration cell is set up and the steel
under the deposit becomes active (anodic) to the passive steel
(cathodic) on the outer surface of the strand. Pitting of
the stainless steel on the inside of the strand under the
deposits will result, which may lead to stress corrosion cracking.
Galvanized steel strand on the other hand will behave quite
differently under similar conditions. The zinc coating on
the galvanized steel strand will protect the steel until the
zinc coating is completely consumed. The outside surfaces
of the strand can show extensive corrosion while the inner
surfaces of the strand are relatively unaffected.
3.2.5 Some metals form tight protective oxide
films that normally resist corrosion. If the film is damaged,
the film will repair itself if sufficient oxygen is present
to oxidize the base metal. In the absence of sufficient oxygen
to keep the oxide film in repair, the metal under the damaged
film becomes active relative to the film protected surfaces
and, as in the case of the oxygen cell, corrosion pitting
will occur under the deposit. Similarly, concentration cell
corrosion may occur on metal surfaces which are covered with
nonmetallic materials. If manufacturing voids, cracks, scratches,
or other accidental openings in a protective coating occur,
moisture can enter under the coating and cause a corrosion
site. Severe pitting may result from local corrosion with
the net damage more severe than if the entire metal area was
exposed to the elements.
3.2.6 Dissimilar surface conditions on a metallic
surface such as scratches or other abrasions and nonhomogeneous
soil backfills can cause galvanic corrosion. For example,
wrench abrasions on a metal surface will be anodic to the
area around it and begin to corrode if there is an electrolyte.
Also dissimilar soils in a backfill will induce galvanic corrosion.
Where rocks and clay in a sand matrix are in contact with
an exposed metal surface, pitting of the metal will occur
from galvanic action.
3.3 Bacteriological Corrosion
3.3.1 Certain types of bacteria can establish
conditions on the surface of underground metallic structures
which will result in more rapid corrosion by existing cells.
The most significant type of bacteria which can cause corrosion
is the anaerobic type which means that the bacteria thrive
in the absence of oxygen. The anaerobic bacterium which is
the most common problem-causing corrosion bacterium is known
as Desulfovibrio Desulfuricans. This form of bacteria reduces
any sulfates present at the underground metal surface to produce
hydrogen sulfide and consumes hydrogen in the process. At
the metallic surface, hydrogen is consumed at the cathodic
surfaces of the existing corrosion cells. This intensifies
the action of the corrosion cell by depolarization. From the
above it is apparent that the bacteria do not themselves attack
the metal, but do result in the intensification of existing
corrosion cells.
3.3.2 Anaerobic bacteria are likely to be
found in heavy, dense, water logged soils where oxygen content
is at a minimum. They can exist, however, under less favorable
conditions or under a material coating which locally restricts
the oxygen content.
3.3.3 Bacteria require organic material as
a food supply. This food supply is normally available to some
degree in the earth. However, if a major food supply is combined
with a restricted oxygen content, the rate of corrosion can
be intensified. An example of this action is a piece of wood
lying against an underground metallic structure.
3.4 Stray Current Corrosion
3.4.1 Stray current corrosion is due to direct
currents of external origin leaving a metal. Since corrosion
is electrochemical in nature, metals ordinarily will corrode
whenever current leaves the metal to pass into the electrolyte,
regardless of the current source. Stray current corrosion
can be caused by dynamic stray current and static stray current.
3.4.1.1 Dynamic stray currents are currents
which change with time. Sources of dynamic stray current can
cause changes in the areas where current enters and leaves
the structure and can cause reversal of current flow on a
structure in some instances. This all results in changes in
the location of the anodic and cathodic areas.
3.4.1.2 Static stray currents are currents
which are from a steady state external dc voltage source which
results in fixed anodic and cathodic areas on the affected
structure with a relatively constant current flow on the structure.
3.4.1.3 Static stray currents tend to be more
corrosive than dynamic stray currents per ampere of current
leaving the underground structure and entering the environment.
This is because the variable characteristics of dynamic stray
currents, particularly where current reversals occur, cause
them to take on some of the characteristics of alternating
current which is relatively an insignificant source of corrosion.
Therefore, the alternating current characteristic of dynamic
stray current tends to reduce its corrosive impact to some
degree. However, dynamic stray currents can cause serious
corrosion problems where large stray currents are encountered.
3.4.2 Stray current corrosion can be either
man-made or natural. Some of the man-made sources of stray
direct current are as follows:
a. Variable speed drives in transit systems;
b. Load-carrying devices;
c. Mining operations;
d. Welding operations; and
e. High voltage direct current electric power
transmission systems.
The natural source of stray current is referred
as telluric or earth current of magnetic origin. These are
direct currents in the earth's crust which result from the
variations in the earth's magnetic field which in turn result
from variations in solar activity. The telluric currents are
dynamic in nature because the anodic and cathodic areas on
the structure are constantly changing as a result of reversals
in the direction of current flow on the structure. The telluric
currents usually affect long structures such as pipelines
and tend to cause more corrosion problems in some parts of
the world other than the United States.
3.4.3 Stray current corrosion was noted years
ago in cities where direct current was used widely in industrial
applications. In the rural areas lead sheathed telecommunications
cables buried by telecommunications companies have been corroded
by cathodic protection applied to cross-country pipelines
to prevent corrosion of the pipelines.
3.4.4 In pipeline cathodic protection, a negative
potential is impressed on the pipeline which causes electrical
earth currents to flow to the pipeline, protecting it against
corrosion. Since the conductivity of most metals exceeds the
conductivity of average soils, buried metallic pipes or cables
act as low resistance paths and tend to collect stray earth
currents which may be present in the surrounding earth electrolyte.
At the point where the stray currents enter these auxiliary
conductors the earth becomes anodic and the pipe or cable
becomes cathodic. But where the currents leave the auxiliary
conductor (a pipe or cable) to enter the cathodically protected
pipeline (See Figure 3), the metallic auxiliary conductor
becomes anodic, and the resulting localized corrosion can
be quite severe.
3.4.5 A comparison of stray current corrosion
to galvanic corrosion reveals several differences. The damage
caused where the direct current from an external source leaves
a grounded metal is independent of oxygen concentration of
the surrounding environment. The flow of stray currents usually
develops sufficient voltage to force hydrogen discharge so
corrosion is not limited to the oxygen reduction reaction.
Likewise, stray current corrosion is not affected by deposits
of corrosion products or protective coatings unless the coatings
are perfect insulators. Defects in the coatings can actually
result in more severe localized corrosion since the current
is concentrated at these sites.
4. CORROSION BEHAVIOR OF METALS USED IN OUTSIDE
PLANT
CONSTRUCTION
4.1 Atmospheric Environments
4.1.1 Corrosive atmospheric environments have
caused REA to become increasingly aware of the need for special
attention in the choice of materials and construction practices.
There are areas of the United States where plant maintenance
and replacement costs are excessively high because of the
corrosive nature of the atmospheres. The atmospheres are grouped
into three general classifications which are industrial, marine,
and rural.
4.1.2 Industrial atmospheres are among the
most corrosive. The atmosphere around industrial plants may
contain sulfur oxides and carbon dioxides in relatively high
concentrations. Sulfur oxide and carbon dioxide both form
acid films on exposed metals and, since most pollutants present
in the atmosphere attract moisture, atmospheres high in these
contaminants usually are very corrosive. Long range transport
of industrial pollutants is responsible for acid deposition
over large areas of the United States.
4.1.3 Marine atmospheres are corrosive because
of the sea air and because of the industry usually located
in those areas. The depth of these coastal areas vary from
approximately three kilometers to as much as thirty kilometers
from the ocean. In some areas, such as along the Gulf Coast
of Louisiana and Texas, typical marine corrosive atmospheres
exist as far inland as 160 kilometers due to a combination
of salt atmosphere and industrial fumes. Sea air contains
chlorides and may contain traces of sulfur, carbon dioxide,
and other components that, over a period of time, can become
concentrated on metal surfaces. Furthermore, in areas immediately
adjacent to the shore, the salt spray from the ocean thrown
up by strong breezes contributes to the buildup of sea salt
deposits on metals which keeps them wet a good portion of
the time.
4.1.4 Years ago, exposed metals were expected
to obtain their longest possible service life in rural atmospheres
which represented approximately 80 percent of the United States.
However, industrial pollutants which consist of sulfur oxides
(SOx) and nitrogen oxides (NOx) are subject to chemical transformation
in the atmosphere to form acids. These pollutants, which can
be carried hundreds and sometimes thousands of kilometers
cause acid deposition over wide areas of the United States.
Consequently rural atmospheres can become corrosive.
4.1.5 Galvanized steel is widely used in the
REA program for both hardware items and cable messenger strand.
In industrial atmospheres the corrosion products formed on
galvanized steel are zinc sulfate and zinc carbonate with
zinc sulfate predominating. The zinc sulfate is soluble and
is washed off by rain and blown off by wind. The zinc carbonate
is removed chiefly by the erosion action of wind driven dirt
and dust. This loss of corrosion products results in an accelerated
deterioration of zinc in industrial atmospheres. The chlorides
present in both industrial and marine atmospheres will attack
the zinc coating on galvanized steel to form a zinc chloride.
This zinc chloride compound will attract and retain moisture
and then will react with other elements in the air to form
zinc oxychloride and zinc carbonate. The resulting coating
is porous and powdery and can be washed off quite easily.
Because of the moisture-laden winds along the coast, corrosion
products can build up faster than the rain can wash them off.
Since the material remains wet most of the time, the corrosion
will progress until the zinc is completely changed to compounds
leaving base steel unprotected. The chemical composition of
the base steel will determine the integrity of the oxide coating
formed after the zinc has been sacrificed. Carbon steel will
develop an oxide coating which will be porous and flaky. The
oxide is not soluble but may be readily dislodged. Thus the
carbon steel will continue to corrode. The oxide coating on
the low alloy steel will be less porous and more adherent
than the oxide on the carbon steel. The rate of diffusion
of corrosive elements to the base metal will be low; consequently,
the low alloy steel will be more corrosion resistant.
4.1.6 Copper and copper alloys, as well as
copper-covered steel, are used to a great extent in the REA
telecommunications program for conductors, shielding, and
a variety of hardware items. Copper is the most sensitive
to the sulfur oxides present in industrial atmospheres. New
copper exposed to an industrial atmosphere will form a copper
oxide coating which is not porous but is quite brittle. The
sulfur dioxide and moisture in the air will combine with the
copper oxide to convert part of it to basic copper sulfate.
Copper corrosion products provide the familiar green patina
appearance on copper. The recognized low rate of copper corrosion
in the atmosphere is due to the protective patina. As long
as the patina is not disturbed, the corrosion reaction will
continue, but at a very slow rate. However, if the cuprous
oxide underlayer is disturbed, fresh copper is exposed anew
to the accelerated corrosion process.
4.1.7 The somewhat protective copper coating
on a copper-covered steel conductor can be dislodged by vibration
or abrasion under tension. Copper and copper-covered steel
will probably corrode at a faster rate in a marine atmosphere
than in an industrial environment because of the presence
of chlorides and traces of sulfur. The surfaces of the metals
are likely to remain wet a large share of the time because
of salt spray. The copper will react with oxygen to produce
a layer of basic copper oxide which is converted to basic
copper sulfate and basic copper chloride in the salt air.
The same copper oxide would be present as in the industrial
environment but its combination with the chloride would cause
the corrosion reaction to be stronger. The coating would probably
be more porous which would hold more moisture and would allow
more air to diffuse through to the base metal to continue
the corrosion of the copper. Because there is a relatively
thin layer of copper over the base steel in the copper-covered
steel conductors, the tendency for the steel to be exposed
to the atmosphere is very real. Once the steel is exposed
to the atmosphere, a galvanic corrosion cell is formed with
the steel anodic to the copper. Since the exposed area of
the steel (anode) is small compared to the area of the copper
(cathode) on the surface of the wire, the galvanic cell that
results is active and the corrosion of the steel will be rapid.
4.1.8 Certain grades of stainless steel have
been used for cable suspension and guy strands in industrial
and marine areas to provide additional service life over that
offered from Class C galvanized steel strand. Corrosion resistant
steel forms a protective oxide coating to corrosive elements
in the industrial and marine atmospheres by preventing moisture
penetration to the base metal. However, when dirt and soot
from industrial atmospheres and salt deposits from marine
atmospheres settle upon the surface and into the interstices
of the strand, an oxygen concentration cell is created. The
corrosion resulting from the concentration cell and the subsequent
stress corrosion cracking of the strand is quite serious.
Cable suspension strand made of stainless steel can appear
perfect but fail because of corrosion pitting inside the strand
that is not apparent from visual inspection. Some outside
plant engineers favor the use of Class C galvanized steel
strand over the corrosion resistant steel because of the oxygen
concentration, stress corrosion phenomenon. Although the Class
C galvanized steel strand has a shortened life span in a corrosive
atmosphere, replacement can be planned whereas the failure
of the corrosion resistant steel strand can not be predicted
with certainty. The serious effects of premature or unexpected
failure of a suspension strand carrying telecommunications
cable should be a significant factor in selecting strand.
4.1.9 In addition to the three basic types
of atmospheres found within the United States, there may exist
commercial operations that could change the characteristics
of the atmosphere in the environment which could result in
accelerated corrosion of telecommunications outside plant
products. Such operations exist in areas of high air pollution
and include drilling or mining installations, chemical or
fertilizer plants, burning slag dumps, sour gas field, etc.
Also in hot humid areas, vegetation such as Spanish Moss can
absorb moisture and in contact with a metallic structure can
create a galvanic corrosion cell which could lead to serious
corrosion. All of the above factors must be considered when
evaluating the possibility of atmospheric corrosion of outside
plant facilities.
4.2 Underground Environments
4.2.1 Underground equipment in the REA telecommunications
program consists of anchors, anchor rods, ground rods, buried
plant terminal housings, and buried cables and wires. A majority
of currently installed telecommunications cable and wire plant
is buried directly in the soil. The various shielding and
armoring materials, when exposed to the environment of different
soils, are subjected to all of the corrosion mechanisms. These
corrosion mechanisms include the effects of dissimilar metals
(galvanic couples), soil conditions, differential aeration,
stray currents, and bacteria. From past experience the corrosion
of anchor rods has proven to be the most important aspect
of outside plant construction. The corrosion of galvanized
steel anchor rods may be caused by dissimilar metal affects
(galvanic couples), soil conditions (differential salt concentration
or differential aeration) or by stray currents.
4.2.2 The general practice has been to use
galvanized or copper-covered steel ground rods for grounding
of metallic facilities or structures. Also a requirement on
joint use construction, where the power system is of the multigrounded
neutral type, is to bond the guy strand to the neutral either
directly or through the cable messenger (suspension strand).
The zinc and iron in a galvanized steel anchor rod, when buried
in conducting earth, tend to develop a dc voltage that is
more negative (anodic) than that of buried copper (cathodic).
When the buried steel and copper are connected together by
the power system neutral, as shown in Figure 4, currents will
begin to flow through the completed circuit from the steel
through the conducting earth to the copper on the ground rod
and the copper pole-butt grounds. Corrosion associated with
such current flow is an example of galvanic corrosion.
4.2.2.1 Polarizing effects occur at the steel
and copper surfaces in most soils and interfere with the flow
of current so that it soon decreases to the point where no
serious damage results. In the more aggressive soils, however,
the current may continue to flow so that the steel is corroded
at an excessive rate. Excessive underground corrosion is generally
noticed on anchor rods first, and in many cases anchor rod
corrosion is believed to be the entire problem, but other
buried structures may be affected. Any buried structure connected
to the power system neutral may be corroded as a result of
galvanic action. Another example of corrosion due to galvanic
action is the connection of telephone system copper covered
ground rods to steel anchors and anchors rods.
4.2.2.2 Ungalvanized anchors are considered
an important contributor to corrosion of steel anchor rods
and may be the major contributor where the corrosion is not
associated with currents in guys due to copper grounds. The
mill scale on hot-rolled steel and oxide films on other steel
is cathodic to galvanized and bright surfaces in much the
same way as copper causes corrosion. Galvanizing of anchors
requires prior removal of all oxide films, and the galvanizing
offers additional corrosion protection to the anchor rod as
well as to the anchor.
4.2.3 Differential aeration corrosion of an
anchor rod can occur, regardless of the material used, even
though it is electrically isolated from the power system's
multigrounded neutral. A differential aeration corrosion cell
(See Figure 5) may begin on the surface of the anchor rod
where the lower portion of the rod, in contact with a soil
low in oxygen, becomes anodic to the upper portion of the
rod which is in contact with a soil having higher oxygen contents.
Most corrosion failures of anchor rods occur within 15 centimeters
of the anchor, and other structures also likely to have the
greatest damage deep in the ground where moisture is present
and oxygen excluded.
4.2.4 Stray currents from cathodic protection
applied to cross-country pipelines have caused REA borrowers
a number of corrosion problems. Stray currents from these
cathodically protected pipeline systems can cause rapid corrosion
of anchor rods, ground rods, metal sheathed cables, and other
metallic structures placed underground. The first signs of
stray current corrosion damage is likely to be failure of
one or more anchor rods in low or wet locations. In the majority
of cases this anchor rod failure can be noted from slack guys.
This initial corrosion signal should initiate an investigation
into the problem before further damage occurs.
5. CORROSION PREVENTION MEASURES
5.1 Atmospheric Environment
5.1.1 The atmospheric environment that exists
in the area of proposed construction should be determined
by the engineer during the early stages in the design of the
telecommunications system. Corrosive atmospheric conditions
may exist over an entire service area of a telecommunications
system or may be confined to relatively small areas within
the total service area. In heavily populated industrial areas
that are spread over several square kilometers, the entire
project area may be corrosive and require special consideration.
On the other hand, in an area that is generally classified
rural, a commercial operation could affect the service life
of just a few kilometers of plant. One of the most valuable
sources of information for the engineer is the historical
performance of the various materials that are being replaced
in a particular area. Obviously, if the material in the plant
being replaced has been in service for 20 to 25 years there
is no reason for serious concern.. When it is not possible
to determine the service life of the existing plant because
of a lack of records or personnel who remember when a certain
section of line was built, the local electric utility may
be able to furnish the necessary information. Many of the
materials and the problems in the use of these materials are
common to both the telecommunications and the electric utilities.
Also a survey of the commercial and industrial activities
in the service area should pinpoint those areas where special
corrosion preventive measures should be taken.
5.1.2 Once the type of atmosphere in the proposed
area of construction has been identified, a determination
of materials best suited for use in that particular environment
should be made. For best results consider areas immediately
adjacent to the east coast and to the northwest coast of the
United States to be marine, whereas the areas within 30 kilometers
of the Gulf Coast of Louisiana and Texas and the coast of
California south of San Francisco would be classified as marine-industrial.
In the Gulf Coast areas of Louisiana and Texas, the belt from
30 kilometers to 160 kilometers from the coast would be classified
as industrial because of the numerous oil wells, chemical
processing, and oil and gas refinery operations.
5.1.3 Galvanized steel has been widely used
for many years in the telecommunications industry for hardware
items. Generally speaking, hardware items such as 3-bolt clamps,
cable suspension clamps, machine bolts, thimble-eye bolts,
etc., are available only in galvanized steel. However, in
the past several years aluminum covered steel and aluminum
alloy hardware items have been developed for use in outside
plant construction. In severely corrosive industrial areas
, where galvanized steel would have a shortened service life,
the use of aluminum covered steel or aluminum alloy hardware
is recommended where available. If the use of aluminum covered
steel or aluminum alloy hardware is not used in these situations,
galvanized steel hardware made from low alloy steel should
be used in preference to carbon steel.
5.1.4 One of the most important considerations
in material selection for a given environment is to choose
metals that will give good performance when fastened together.
Metals that are widely separated in the galvanic series (Table
1) should not be placed in contact with one another. If the
use of dissimilar metals cannot be avoided, then remember
that the least damage occurs when the ratio of exposed area
of noble (protected) to the exposed area of less noble (corroding)
metal surfaces is kept as small as possible. Also, stranded
wire used for bonding purposes should be tinned copper to
minimize corrosion from joining dissimilar metals. When grounding
wire is required to contact the soil, the bare copper should
be insulated. Whenever possible a connection of dissimilar
metals should be coated. When properly applied, the coating
materials will prevent moisture and air from contacting the
dissimilar metal connection and thus prevent galvanic corrosion
at the jointing interface.
5.1.5 Galvanized steel has been used for many
years in the telecommunications industry for cable messenger
strand and for guy strand. The material is not adequate for
applications in the more corrosive industrial and marine atmospheres.
Experience to date indicates that aluminum-covered steel messenger
strand and guy strand should be used in areas high in sulfur
content, such severely corrosive industrial atmospheres and
near sulfur mining activities.
5.1.6 Polyethylene jacketed and insulated
facilities are expected to experience good performance characteristics
in all types of atmospheres. Theses products should be installed
in areas that are highly corrosive.
5.2 Underground Environments
5.2.1 Corrosion of underground telecommunications
systems is the most difficult to prevent because of the many
factors that singly, or in combination, affect the course
of the electro-chemical reaction. The major problem in corrosion
prevention is to decide the corrective measures that will
give satisfactory results at the least cost. Care must be
taken to insure that the corrective measures taken to cure
the corrosion does not reduce the intended performance of
the telecommunications system. The important need is to adequately
recognize the processes that are happening or can happen and
the alternatives available, so that future corrosion problems
can be minimized. There should be no need to reengineer for
corrosion each time that a system is designed, constructed,
or modified.
5.2.2 The guidelines set forth in the following
paragraphs are intended to minimize underground corrosion
of buried metal that is connected to or a part of the electrical
grounding system and to reduce the difficulty and the cost
of applying cathodic protection where needed for further reducing
the amount of underground corrosion.
5.2.2.1 Galvanic corrosion, caused by connecting
dissimilar metals underground, has been the most prevalent
and most serious type of corrosion experienced by the telecommunications
and electric utility industries. In order to eliminate or
to minimize galvanic corrosion of galvanized anchor rods,
plumbing and well casings, and other metals connected to the
grounding system, REA suggests that grounding of electrical
protection apparatus on telecommunications systems follow
the guidelines contained in this bulletin.
5.2.2.2 Where a driven ground rod is required
for electrical protection (grounding) of the subscriber's
premise in buried plant construction, a galvanized steel ground
rod should be used.
5.2.2.3 On pole line construction, where a
driven ground rod is required for electrical protection purposes
and is to be interconnected with the guy and anchor assemblies,
a galvanized steel ground rod should be used. In the event
the ground rods are not interconnected with the guy and anchor
assemblies, a copper-covered steel ground rod may be used.
5.2.2.4 Where joint use construction is contemplated
with a multigrounded neutral power system inquiries should
be made of the electric company as to its history of underground
corrosion. A corrective program may have already been established.
If so, the telecommunications system should follow a similar
program. If there has been no experience of underground corrosion
on the electric system, standard telecommunications construction
practices can probably be followed with satisfactory results.
5.2.2.5 The use of galvanized anchors, in
addition to the galvanized anchor rods, will further reduce
the rate of corrosion. A substantial amount of protection
against corrosion can be achieved at very little increase
in cost. This is especially important in areas of low earth
resistivity.
5.2.2.6 Stray current corrosion, resulting
from cathodic protection, can be reduced in underground telecommunications
plant by either electrically insulating the telecommunications
facilities from the stray currents or installing a mitigation
bond between the telecommunications facilities and the foreign
structure being cathodically protected. Usually the anchor
rods and anchors can more easily and more economically be
protected by insulating them from the dc source; however a
mitigation bond can easily be provided between the dc source
and the multigrounded neutral. If stray current corrosion
is being experienced on buried metallic sheathed cables, the
best method for reducing its effects probably will be to install
a mitigation bond.
5.2.2.7 When new construction is being contemplated
in the vicinity of a buried pipe system, municipal water system,
or a gas utility system, a determination should be made as
to the corrosion protection measures being employed between
the telecommunications facilities and the foreign structure
being cathodically protected. Every effort should be made
to outline a program with these companies that will assure
the telecommunications facilities of the maximum practical
corrosion protection from the effects of these cathodically
protected foreign structures. Figure 6 shows an example of
a coordinated effort to arrest the corrosive effects on the
buried cable of the stray currents generated by the cathodic
protection applied to the pipeline. A mitigation bond was
placed between the buried metal shielded cable and the cathodically
protected pipeline to provide a low resistance path back to
the rectifier station for the stray currents.
6. ENVIRONMENTAL CONDITIONS AFFECTING THE
SELECTION OF
CABLE OR WIRE SHIELDS
6.1 Many factors, such as construction personnel,
equipment, rock, etc., can damage the cable or wire sheath
during construction. Manufacturing defects, lightning, and
rodents can also contribute to sheath damage. A greater incidence
of sheath damage is experienced in gopher areas and exposure
of the metallic shield is more prevalent. Filled cable and
wire designs and good construction practices have substantially
reduced sheath damage, but are not likely to eliminate it
completely. The proper selection of shielded cable or wire
for use in problem areas will provide maximum corrosion protection
for buried cable or wire.
6.2 The evaluation of the corrosivity of a
soil is complex. Some of the soil properties that affect corrosion
are soil resistivity, stray currents, pH, drainage or aeration,
moisture content, and soluble salts present. Studies sponsored
by REA have shown that NO SINGLE PROPERTY OF A SOIL is an
accurate indicator of its corrosivity to a particular metal.
6.3 Shields incorporating copper, copper alloys,
and copper/alloy steel and copper/stainless steel combinations
comprise a significant portion of the cable or wire system.
Copper exhibits slow, uniform corrosion in most soil conditions.
However, in highly acidic or in sulfur-containing soils, corrosion
of copper may accelerate. Because copper is cathodic to most
metals in the outside plant (i.e., carbon steel or cast iron),
it will receive cathodic protection from these metals within
reasonable proximity, thus extending its life. However, in
newer installations the water and gas systems are often nonmetallic
or electrically insulated, which eliminates the cast iron
or steel as a sacrificial anode. When galvanically coupled
with other copper structures such as power system neutrals,
these shields are not susceptible to accelerated corrosion.
In many environments copper exhibits satisfactory corrosion
resistance; however in an aggressive environment copper may
corrode.
6.3.1 When certain chemical constituents are
present in the soil such as sulfides, bicarbonates, and ammonium
compounds, corrosion of copper can occur. In soils contaminated
by fertilizers, cinders, and decaying organic matter, the
rate of corrosion will be greater than that observed in less
aggressive environments.
6.3.2 Marine and industrial environments,
which may transport pollutants great distances, frequently
contain sulfur compounds such as hydrogen sulfide which may
permeate the jacket and cause corrosion of copper. The soils
containing sulfate ions and anaerobic, sulfide generating
bacteria have in some isolated instances also caused treeing
of the cable or wire jacket.
6.3.3 Copper clad stainless steel or copper
clad alloy steel laminates have demonstrated satisfactory
corrosion resistance in tests and in service in a wide range
of environments. The outer layer performs comparably to solid
copper and to copper alloys in soils where copper has satisfactory
corrosion resistance. In more aggressive soils i.e., low pH,
high sulfide levels, where copper corrosion is accelerated,
test and fields results have shown that the stainless steel
or alloy steel remains passive and acts as a corrosion barrier
protecting the inner copper layer from corrosion. Thus the
shield integrity may be prolonged.
6.3.4 The primary mechanisms which can contribute
to the corrosive attack of copper are as follows:
a. Direct attack in acidic, sulfide, and ammonia
containing soils;
b. Electrolytic corrosion from external sources
of
direct current; and
c. Corrosion under the influence of alternating
current.
6.4 The use of plastic coated aluminum since
the early 1960's indicates its use as one approach in controlling
corrosion for shields in buried cables used in the outside
plant. Plastic coated aluminum has demonstrated satisfactory
corrosion resistance in fields tests, laboratory tests, and
service in a wide range of environments for over 25 years.
Note: For uniformity, the words coated and
coating are
used in this bulletin to describe metallic
components
covered with plastic materials whether by
solvent release
coating, film laminating or extrusion coating.
The intent
of the reference is to address the performance
of the
coated materials, not to describe the process
of
preparation.
6.4.1 The plastic coating restricts the area
of aluminum subjected to corrosion. The polymer coating forms
a chemical bond with the metal which effectively counteracts
the mechanical forces generated during the corrosion process
that attempt to detach the coating. Also, the chemical bond
prevents the migration of moisture and chemicals along the
interface of the copolymer coating and aluminum thus retarding
corrosion.
6.4.2 The forces which damage the outer jacket
also will likely damage the plastic coating. In this case,
localized corrosion of the aluminum may occur wherever the
coatings are damaged due to the same factors which corrode
bare aluminum. However, coatings which are chemically bonded
to a metal substrate will generally restrict the corrosion
to the vicinity of the damaged region. In outside plant areas
where the jacket is more susceptible to mechanical damage,
the coated aluminum should be bonded to the jacket since bonded-sheath
improves the puncture resistance and toughness of the cable
and thus reduces the possibility of cable damage.
6.4.3 Since galvanized steel is recommended
for use as ground rods, galvanic corrosion of the plastic
coated aluminum shield is greatly reduced. However, where
the plastic coated aluminum shield is coupled to a copper
shield, careful consideration needs to be given to the area
of cathode (copper), anode (coated aluminum), and distance
of the electrolyte between the metals.
6.4.4 If the plastic coating on the aluminum
is damaged, corrosion may be initiated. Factors which are
likely to corrode the bare aluminum are as follows:.
a. Direct attack in soils;
b. Galvanic corrosion;
c. Dynamic and static stray currents from
external
sources; and
d. Differential aeration.
Aluminum is an amphoteric metal and it corrodes
more rapidly in highly acidic and highly alkaline media, i.e.,
at pH levels below 5.0 and greater than 8.5. The rate of corrosion
also depends on the specific ions present. Chlorides and sulfates
are considered aggressive towards aluminum. Also when aluminum
is coupled to copper and other passive metals, corrosion of
aluminum can be severe due to galvanic effects. Although these
mechanisms are pertinent to exposed bare aluminum at defects
in plastic coated aluminum, the rate at which corrosion occurs
for plastic coated aluminum is mitigated by the presence of
the plastic coating, as described in the previous paragraphs.
6.4.5 Marine and industrial environments,
which may transport pollutants great distances, frequently
contain sulfur compounds such as hydrogen sulfide which may
permeate through the jacket and cause corrosion.
6.4.6 The primary mechanisms which can contribute
to the corrosive attack of bare aluminum are:
a. Direct attack in highly acidic and highly
alkaline soils;
b. Chlorides and sulfates;
c. Electrolytic corrosion from external sources
of
direct current;
d. Corrosion under the influence of alternating
current;
e. Galvanic effects when coupled to copper;
f. Galvanic effects when coupled to other
passive metals;
and
g. Differential aeration.
6.5 The corrosion of bare steel due to the
various factors thus far described for aluminum and copper
in the text is well recognized. Bare steel is more susceptible
to corrosion in acidic rather than neutral or alkaline media.
The plastic coatings on both aluminum and steel reduce the
corrosion from the environment. The use of coated steel provides
the first line of defense from corrosive elements if the jacket
is damaged and also protection to the coated aluminum for
it to perform vital shielding functions. If the plastic coating
on the steel is damaged, corrosion may be initiated with subsequent
dissolution of the steel. Further corrosion of the exposed
steel may proceed according to the primary mechanisms referenced
in Paragraph 6.4.6.
6.6 Certain locations in the country may have
severe corrosion conditions which are more harmful to one
type of cable or wire shield or cable armor than another.
In such areas, the engineer should determine the cable or
wire material which is best suited for these particular soil
conditions. To determine a potentially corrosive environment,
the engineer should measure the earth resistivity, identify
the pH level of the soil, and gather historical data from
company files and from other utilities in the exchange area.
Soil resistivity is an indicator of corrosivity as shown in
Table 2; as well as, is historical data. However, the latter
should be viewed in light of changing soil conditions caused
by acid rain, long-range transport of industrial pollutants
in the atmosphere, deicing practices, fertilizers, etc. If
there has been no prior construction in the vicinity of a
new site, the soil resistivity and pH at the new site should
be determined and compared to measurements taken at similar
sites with some long-term in place construction. For example,
if soil measurements along a new cable or wire route indicate
a neutral pH with low soil resistivity and a similar site
with long lived coated aluminum cable plant is nearby with
a good performance history, coated aluminum shielded cable
could probably be used at the new site with no problems.
TABLE 2
Soil Corrosivity Versus Resistivity
Soil
Resistivity Corrosivity
(Ohm·cm) (description)
Below 500 Very Corrosive
500 to 1000 Corrosive
1000 to 2000 Moderately Corrosive
2000 to 10,000 Mildly Corrosive
Above 10,000 Progressively Less Corrosive
6.7 Soil properties can be obtained from the
local Soil Conservation office or samples can sent to an independent
laboratory for property measurements. Soil resistivity is
the easiest measurement and should be made on site following
the recommended techniques listed in Section 7. Figures 7
through 11 show the general soil resistivity throughout the
United States but are not meant as a substitute for local
measurements.
7. SOIL MEASUREMENTS
7.1 Soil Resistivity
7.1.1 Soil resistivity can be measured in
a number of ways. The most accurate method is to obtain some
soil at the cable or wire burial depth and measure the resistivity
in the laboratory under controlled conditions which include
saturating the soil with distilled water. A field measurement
can be made at the soil burial depth using the four terminal
method shown in Figure 12. Four small test electrodes (stubs
of number 8 American Wire Gauge (AWG) wire will suffice) are
placed to the same depth and equal distances apart in a straight
line. Four separate lead wires connect the electrodes to the
four terminals on the soil resistivity tester as shown in
Figure 12. Hence, the name of the test: The Four Terminal
Method.
7.1.2 The theory behind the Four Terminal
Method showed that if electrode depth A is kept small compared
to the distance between electrodes B, the following equation
applies:
P = 2ÐBR
Where:
P = Average soil resistivity to depth B in
ohm·cm
Ð = 3.1416
B = Distance between electrodes
R = Instrument reading in ohms
7.1.3 Since copper cable or wire is usually
buried at a depth of 0.6 to 1 meter (m), the average soil
resistivity should be measured to at least 1.2 m. For buried
fiber optic cable, the average soil resistivity should be
measured to at 1.5 m because this cable is usually buried
at a depth of 1 to 1.2 m. Where a cable is to be buried at
a depth greater than 1.2 m, the average soil resistivity should
be measured at the 1.2 m depth plus 25 percent. The electrode
depth should not exceed 10 percent of the electrode spacing
dimension. A 7.6 centimeter (cm) electrode depth should be
adequate. Black vinyl tape may be placed 7.6 cm from the ends
of the electrodes as a depth gauge. Assuming an instrument
reading of 30 ohms is obtained at 1.2 m electrode spacing,
the soil resistivity would be calculated as follows:
P = 2ÐBR
= 2 * (3.1416) * (1.2 m x 100 cm/m) * (30)
= 754 * (30 ohms)
= 22,620 ohm·cm
Therefore, if the 1.2 m electrode spacing
is maintained the soil resistivity is 754 times the instrument
reading in ohms. If an electrode spacing of 0.86 m is maintained
a multiplier of 500 will result yielding resistivity at 0.86
m which is a realistic cable or wire placement depth. Typical
soil resistivity values to be expected are given in Table
3.
TABLE 3
Typical Soil Resistivity Values
Soil
Resistivity
Soil Types (Ohm·cm)
Sand Saturated with Sea Water 100 - 200
Marsh 200 - 400
Clay 200 - 15,000
Sand and Gravel 5,000 - 100,000
Clay Mixed with Sand Gravel 1,000 - 135,000
Shale 1,000 - 50,000
Rock 50,000 - 1,000,000
Limestone 500 - 400,000
Note: A description of the Four Terminal Method
is
described in ASTM G 57, latest issue, Standard
Method for
Field Measurement of Soil Resistivity Using
the Wenner
Four Electrode Method.
7.2 Soil pH
7.2.1 Soil pH can be measured with a number
of commercially available battery-powered meters. These high-impedance
meters measure the potential difference between a sensing
electrode whose potential changes with the hydrogen ion concentration
and a reference electrode (usually calomel). Commercially
available combination electrodes consisting of a saturated
calomel reference electrode and an electrode combined as one
single electrode are available. The easiest and most practical
method to measure soil pH is the use of a commercial meter
in conjunction with a combination electrode.
7.2.2 The pH meter and electrodes are standardized
by immersion in standard solutions of known pH and adjustment
of the standardized dial in accordance with the manufacturers'
recommendations or ASTM G 51, latest issue.
7.2.3 The contact area of the glass electrode
or combination electrode should be pressed against undisturbed
soil at the location of interest. With the electrodes in place,
set the meter to read pH, allow sufficient time for equilibrium
to be established, then take the meter reading. Again allow
the meter to equilibrate, then reread the meter. The values
obtained should agree within 0.2 units to be acceptable.
7.2.4 It is best to bore and make the pH measurement
at the depth of interest. A subsurface probe for accomplishing
this is described in ASTM G 51, latest issue, Standard Test
Method for pH of Soil for Use in Corrosion Testing. Soil samples
can be brought to the surface with a boring tool or post-hole
digger and the measurement made in the field on the soil thus
obtained. The least desirable method is to make the measurement
on soil returned to the laboratory, however, if this is done
the measurement should be made within 24 hours from the time
the sample was obtained. Under no circumstances should a surface
pH measurement be construed as the pH of the soil at the cable
depth.
CLICK
HERE FOR PRINTABLE VERSION
|