| Design
of Buried Plant, Physical Considerations
UNITED STATES DEPARTMENT OF
AGRICULTURE
Rural Utilities Service
BULLETIN 1751F-640
SUBJECT: Design of Buried Plant - Physical
Considerations
TO: All Telecommunications Borrowers
RUS Telecommunications Staff
EFFECTIVE DATE: Date of Approval
EXPIRATION DATE: Seven years from effective
date
OFFICE OF PRIMARY INTEREST: Outside Plant
Branch, Telecommunications Standards Division
PREVIOUS INSTRUCTIONS: This bulletin replaces
RUS Telecommunications Engineering & Construction Manual
(TE&CM) Section 640, Design of Buried Plant - Physical
Considerations, Issue 4, dated May 1973 and File With, dated
June 1967.
FILING INSTRUCTIONS: Discard RUS Telecommunications
Engineering & Construction Manual (TE&CM) Section
640, Design of Buried Plant - Physical Considerations, Issue
4, dated May 1973, and File With dated June 1967, and replace
it with this bulletin. File with 7 CFR 1751 and on RUSNET.
PURPOSE: This bulletin provides RUS borrowers,
consulting engineers, contractors and other interested parties
with information on the design and construction of buried
plant facilities.
Wally Beyer 3/3/95
______________________________ __________________________
Administrator Date
TABLE OF CONTENTS
1. General .................................................
4
2. Application .............................................
5
3. Construction Materials ..................................
9
4. Mechanical Protection Guards and Rodent
and
Insect Control .........................................
10
5. Design Considerations ..................................
11
6. Economic Considerations ................................
12
TABLES & FIGURES
Figure 1 Gopher Infested Areas ............................
14
INDEX:
Outside Plant
Design
Telecommunications
ABBREVIATIONS
BFC Buried Filled Cable Assembly Unit
BFO Buried Filled Fiber Optic Cable Assembly
Unit
CATV Community Antenna Television
LD Loan Design
NEC National Electrical Code
NESC National Electrical Safety Code
P Suffix for a Predesignated Area Assembly
Unit
R/W Right-of-way
RUS Rural Utilities Service
SAVE Serving Area Value Engineering
STMP State Telecommunications Modernization
Plan
TE&CM Telecommunications Engineering and
Construction Manual
DEFINITIONS
BFC: A buried filled cable assembly unit which
includes all the material and labor costs to plow or trench
and backfill
1,000 feet (304.8 meters) of filled buried
copper cable.
BFO: A buried filled fiber optic cable assembly
unit which includes all the material and labor costs to plow
or trench and backfill 1,000 feet (304.8 meters) of filled
buried fiber optic cable.
P: A assembly unit suffix which informs the
contractor that installation in that particular area will
be much more difficult than normal because of the presence
of underground facilities or severe right-of-way restrictions.
Loan Design: A comprehensive engineering plan
for the project used to support a loan application to RUS.
Resident Engineer: The representative of the
Engineer who is delegated full time "on site" engineering
responsibilities for construction administration.
RUS accepted (material and equipment): Equipment
which RUS has reviewed and determined that:
a. Final assembly is conducted within the
United States, Mexico, or Canada or any of their territories
and the cost of components within the material or equipment
which are manufactured within the United States, Mexico, or
Canada, or any of their territories, cost more than 50 percent
of the total cost of all components utilized in the material
or equipment, and
b. The material or equipment is suitable for
use on systems of RUS telephone borrowers.
RUS technically accepted (material and equipment):
Equipment which RUS has reviewed and determined that:
a. Final assembly is not conducted within
the United States, Mexico, or Canada, or any of their territories,
or the cost of components within the material or equipment
which are manufactured within the United States, Mexico, or
Canada, or any of their territories, cost 50 percent or less
than the total cost of all components utilized in the material
or equipment, and
b. The material or equipment is suitable for
use on systems of RUS telephone borrowers.
1. GENERAL
1.1 This bulletin discusses in particular
the design of buried plant using filled copper cables, filled
copper wires, and filled fiber optic cables. The information
and recommendations in this bulletin are advisory.
1.2 Buried plant refers to telecommunications
copper cables, copper wires, and fiber optic cables that are
buried directly in the ground by plowing and/or trenching.
1.3 Additional information for the use in
the design and construction of buried plant facilities can
be found in following Rural Utilities Service (RUS) documents:
a. Telecommunications Engineering and Construction
Manual
(TE&CM) Section 116, Plant Engineering
and Record
System, (Proposed conversion to RUS Bulletin
1751B-101);
b. TE&CM Section 210, Telephone System
Design - Sizing
Criteria (Proposed conversion to RUS Bulletin
1751B-204);
c. TE&CM Section 218, Plant Annual Cost
Data for System
Design Purposes (Proposed conversion to RUS
Bulletin
1751B-230);
d. TE&CM Section 219, Present Worth of
Annual Charge
Studies for System Design (Proposed conversion
to
RUS Bulletin 1751B-230);
e. TE&CM Section 230, General Principles
of Feeder -
Distribution Cable Engineering (Serving Area
Value
Engineering(SAVE)) (Proposed conversion to
RUS Bulletin
1751B-230);
f. TE&CM Section 231, Design Techniques
of Feeder -
Distribution Cable Engineering (SAVE) (Proposed
conversion to RUS Bulletin 1751B-230);
g. TE&CM Section 232, Transmission Design
Cost
Considerations of Feeder - Distribution Cable
Engineering (SAVE) (Proposed conversion to
RUS Bulletin
1751B-230);
h. TE&CM Section 424, Design Guideline
for
Telecommunications Subscriber Loop Plant (Proposed
conversion to RUS Bulletin 1751B-101);
i. TE&CM Section 628, Plastic-Insulated
Cable Plant Layout
(Proposed conversion to RUS Bulletin 1751F-628);
j. TE&CM Section 629, Cable Plant Layout
- Serving Area
Concept for Rural Systems (Proposed conversion
to RUS
Bulletin 1751F-629);
k. TE&CM Section 641, Construction of
Buried Plant
(Proposed conversion to RUS Bulletin 1751F-641);
l. TE&CM Section 648, Serving Area Value
Engineering (SAVE)
(Physical Plant) (Proposed conversion to RUS
Bulletin
1751F-648);
m. TE&CM Section 816, Electrical Protection
of Buried Plant
(Proposed conversion to RUS Bulletin 1751F-815);
n. RUS Bulletin 345-150, Specifications and
Drawings for
Construction of Direct Buried Plant, Form
515a (Proposed
conversion to RUS Bulletin 1753F-001);
o. RUS Bulletin 344-3, "Buy American"
Requirement, as
amended by the North American Free Trade Agreement
Implementation Act (NAFTA Act);
p. RUS Bulletin 1751F-642, Staking of Buried
Plant
q. RUS Bulletin 1751F-670, Outside Plant Corrosion
Considerations);
r. RUS Bulletin 1751F-801, Electrical Protection
Fundamentals;
s. RUS Bulletin 1751H-601, Lightwave Fundamentals;
t. 7 Code of Federal Regulations (CFR) 1751,
Subpart B,
State Telecommunications Modernization Plan;
u. 7 CFR 1753.6, Standards, Specifications,
and
General Requirements; and
v. 7 CFR 1755.200, RUS Standard for Splicing
Copper and
Fiber Optic Cables.
2. APPLICATION
2.1 Buried plant facilities offer certain
advantages over aerial and underground plant (in conduit)
facilities, and are more economical on a first cost basis.
Exceptions where this economic advantage may not be realized
are in urban and suburban areas or extensive rock formations.
In these areas, a combination of buried and aerial plant facilities
may prove to be the most economical construction for the system.
In certain situations, the use of underground plant facilities
in conjunction with buried plant facilities may be advantageous.
For these type applications, refer to RUS TE&CM Section
643, Underground Conduit and Manhole Design and Construction
(Proposed conversion to RUS Bulletin 1751F-643).
2.2 Since buried plant facilities are exposed
to less physical damage than aerial plant facilities, fewer
cable or wire faults are associated with buried plant facilities.
This lower fault rate results in longer periods of maintenance-free
operation and greater subscriber satisfaction. Buried plant
facilities should be used in those areas susceptible to frequent
ice storms and/or high wind velocities.
2.3 Permission from appropriate authorities
should be obtained before burying copper cables, copper wires,
and fiber optic cables in public and private right-of way
(R/W). In most circumstances cooperation with appropriate
R/W authorities can be obtained when buried plant construction
techniques are fully explained. Low cost placement of cable
or wire is obtainable when the burial depth of the cable or
wire can be maintained throughout the public R/W. Use of private
R/W for placement of cable or wire should only be considered
if placement would be more economical than in the public R/W.
If public R/W is to be used for placement of the cable or
wire, a comprehensive investigation should be made as to possible
highway improvements, such as widening or changing grade elevations,
since these highway improvements may result in costly future
rearrangements and rerouting. When installing buried plant
facilities at railroad crossings, in navigable streams, and
the crossing of facilities owned by other utilities, the need
for permits should be thoroughly investigated.
2.4 In urban and suburban areas, other buried
facilities such as water lines, gas lines, sewer lines, Community
Antenna Television (CATV) lines, electric and/or telecommunications
lines present obstacles to plowing or trenching. When the
above buried obstacles are anticipated, detailed information
should be obtained from the other utilities on present and
proposed buried facilities locations. Where it is known that
buried obstacles will be encountered during construction,
those areas should be identified separately in the Loan Design
(LD).
2.5 The buried filled copper cable and wire
and buried filled fiber optic cable units for the areas containing
the buried obstacles listed in the LD should be suffixed with
the letter "P." The "P" suffix distinguishes
these units from the normal "BFC" units for copper
cable and wire and the normal "BFO" units for fiber
optic cables in order that the higher cost associated with
installing buried plant facilities in these congested areas
will be included in the project cost estimate.
2.6 Physical Location
2.6.1 The location of buried copper cable
or wire and fiber optic cable should be determined in conjunction
with federal, state, county, and local authorities, and private
interests as applicable. Special attention should also be
given to the type and size of equipment that will be required
to perform the installation.
2.6.2 Some of the considerations that can
affect the physical locations of the buried plant facilities
are:
a. Width of road shoulders;
b. Type of terrain;
c. Type of road;
d. Easements;
e. Fence locations;
f. Required number of buried outside plant
housings;
g. Public and private R/W;
h. Type of drainage ditches;
i. Soil conditions;
j. Railroad crossings;
k. Navigable streams or other bodies of water;
and
l. Environmentally sensitive areas.
2.6.3 When cable or wire is to be installed
in public R/W, discussions with department of transportation
authorities should be held to inform the authorities as to
the location and depth of the buried cable or wire in the
R/W, the placement of a buried warning tape above the cable
or wire, and the placement of above ground warning and route
signs as methods of protecting the buried plant facilities
against damage.
2.6.4 The same procedure as outlined in Paragraph
2.6.3 should be followed in coordination with town and development
areas where buried plant facilities are to be installed. Assistance
should be given to town planning authorities, land, industrial,
and commercial developers by either identifying on existing
construction drawings or in the preparation of new construction
drawings, the locations and depths of all buried plant facilities.
Here again, these organizations should be informed that the
borrower will provide identification and location of its existing
buried plant facilities when requested.
2.6.5 Proposed buried plant construction activities
should be coordinated with other utilities. This coordination
is necessary not only for joint occupancy construction, but
also to properly develop a working relationship between the
various utilities on future planning of all utility plant.
Construction drawings of telecommunications plant to be constructed
should be provided to each of the utility companies whose
plant is, or may be placed, within the area of the borrower's
telecommunication plant facilities.
2.7 RUS Bulletin 345-150, Specifications and
Drawings for Construction of Direct Buried Plant, Form 515a,
provides the minimum required depths for installing cable
or wire in soil, at ditch crossings, and in rock. The resident
engineer should determine the local conditions which would
require the burying of cable or wire at greater depths than
the minimum depths specified in RUS Form 515a. In areas where
crop plowing or subsoil operations are preformed, burying
the cable or wire at increased depths to protect the cable
or wire from damaged may be necessary. The resident engineer
should check with federal, state, county, and local authorities
in regard to any existing and/or proposed land development
programs which would require special design considerations.
2.8 In areas where frost heaving can be expected,
the cable or wire should be buried below the frost line. Movement
of outside plant housings due to frost heaving can cause damage
to the insulated copper conductors, optical fibers, or loss
of shield and/or armor continuity. In areas where movement
of outside plant housings by frost heaving is encountered,
the outside plant housings should be installed on stub poles.
The stub poles should be set below the frost line and in accordance
with the requirements of RUS Form 515.
2.9 In many areas of the United States a problem
of general flooding should be considered in the design and
construction of buried plant facilities. Flooding can also
be a problem within specific areas of a system not included
in the general flood areas. Particular attention should be
given with respect to the routing and depth of the buried
cable or wire in those areas subjected to flooding to prevent
exposure of the cable or wire as a result of soil erosion.
Another consideration in areas subjected to flooding is to
mount outside plant housings onto existing or new poles above
the flood water levels.
2.10 Large areas of the United States as indicated
in Figure 1 are infested with gophers or other rodents which
can damage buried plant cables and wires. This damage can
lead to corrosion of metallic elements within the cables and
wires, copper conductor insulation damage, broken optical
fibers, loss of cable shield and/or armor continuity, service
interruptions, etc. RUS specifications for filled copper cables
and wires, and the RUS specification for filled fiber optic
cables includes designs that are recommended for burial in
gopher and rodent infested areas. Although Figure 1 indicates
areas with significant gopher infestation, the resident engineer
should thoroughly investigate the project area and should
contact the local agent of the U. S. Department of Agriculture,
Animal and Plant Health Inspection Service, before determining
if a rodent resistant cable or wire design is required for
the project area.
2.11 One of the important responsibilities
of the resident engineer in the design of buried plant facilities
is the providing of above-ground identification of the buried
plant facilities. This can be accomplished by the installation
of warning and cable route signs along the construction route.
The warning and cable route signs should provide information
as to identification and proper instructions in order to avoid
service interruptions. The resident engineer should provide
information as to the number and spacing of signs along the
cable route to clearly define the location of the buried plant
facilities to the telecommunications company personnel and
to the general public. The signs should be installed adjacent
to the cable or wire along roads, railroads, pipe lines, streams,
irrigation and drainage ditches, and at other locations where
it is likely that excavation work may occur. In addition,
the signs should also be installed at each change in route
direction, at buried splice locations, etc. Where practicable,
signs should be placed in fence lines or at other locations
where they will not inconvenience the property owner on private
R/W. The type of signs and examples of sign layout drawings
are included in RUS Bulletin 345-150, Form 515a. In certain
situations the resident engineer may require the installation
of a brightly colored below-ground warning tape above the
cable along with the above-ground identification to provide
addition protection against service interruptions.
3. CONSTRUCTION MATERIALS
3.1 For all buried plant construction projects
financed with RUS loan funds, RUS regulation 7 CFR 1753.6
requires that only RUS accepted materials be used.
3.2 RUS technically accepted, nondomestic
manufactured materials, may also be used on buried plant construction
projects.. Before technically accepted materials can be used
on buried plant construction projects, permission is required
from the
RUS borrower. In addition, borrower's are
required to ensure that the cost of the technically accepted
materials are at least 6 percent less than the cost of the
RUS accepted materials, as specified in RUS Bulletin 344-3,
"Buy American" Requirement, as amended by the North
American Free Trade Agreement Implementation Act (NAFTA Act).
4. MECHANICAL PROTECTION GUARDS AND RODENT
AND INSECT CONTROL
4.1 When the minimum depth of the cable or
wire cannot be obtained as indicated in Paragraph 2.7, metallic
or nonmetallic split "U" or spirally cut guards
or preservative treated planks should be installed to provide
mechanical protection to buried cable or wire, or direct buried
splice cases and load coils.
4.1.1 The metallic or nonmetallic split "U"
or spirally cut guards should be used to protect the cable
or wire at the following locations:
a. Road, street, or highway crossings;
b. Open drainage ditch crossings;
c. Foreign pipe, cable, or wire crossings;
and
d. Stream and river crossings.
4.1.2 The preservative treated planking should
be used to protect the cable or wire at the following locations:
a. Parallel runs within highway R/W if required
by
regulations;
b. Within railroad R/W if required by regulations;
and
c. In exposed areas susceptible to hand or
mechanical
digging.
4.2 Nonmetallic split "U" guards
or small diameter conduits should be used at buried service
entrance installations to protect the exposed portions of
buried service wires from possible subscriber damage.
4.3 Preservative treated planks should be
installed at direct buried filled splice case and direct buried
load coil case locations to protect the splice and load coil
cases from mechanical damage.
4.4 Rodent And Insect Control: Rodent and/or
insect repellant should be installed in outside plant housing
locations where damage to copper conductors or fiber optic
cable from mice, ants, termites, etc., could occur.
5. DESIGN CONSIDERATIONS
5.1 Buried plant construction should be the
method of construction when the initial construction cost
is equal or lower than the initial construction cost of aerial
plant construction and when the annual cost of the buried
plant facilities are lower than the annual cost of aerial
plant facilities.
5.2 Buried plant construction should also
be considered in areas which may have previously been assumed
to be uneconomical because of costs, materials, construction
techniques, etc., when such factors indicate that economical
buried plant construction costs in these areas can now be
achieved.
5.3 Joint burial of electric and telecommunications
cables should only be considered when required by local, State,
or Federal ordinances or regulations. When joint burial of
electric and telecommunications cables is considered, the
design and construction of the joint occupancy facilities
should be performed in accordance with the latest editions
of the National Electrical Code (NEC), National Electrical
Safety Code (NESC), local or State regulations, or Federal
regulations. When the local, State, or Federal regulations
are more stringent than the NEC or NESC codes, the more stringent
requirements should be observed. When joint burial is necessary,
every effort should be made to limit the length of exposure
to 1/2 mile (0.8 km) to minimize the possibly of induction
of power line harmonics in telecommunications circuits which
may create objectionable noise conditions for telecommunications
subscribers.
5.4 For outside plant buried facilities using
copper cables, circuit requirements should be thoroughly evaluated
to provide sufficient margin in the sizing of both buried
distribution and feeder cables. The sizing of the copper cables
should be based on the recommendations listed in RUS TE&CM
Section 210, Telephone System Design - Sizing Criteria. The
assigning of cable pairs should be based on the recommendations
included in RUS TE&CM Section 629, Cable Plant Layout
- Serving Area Value Engineering for Rural Systems.
5.5 For outside plant buried facilities using
fiber optic cables, circuit requirements should be thoroughly
evaluated to provide sufficient margin in the sizing of the
cables. The sizing of the fiber optic cables should be based
on circuit requirements of the LD plus the number of circuits
needed for future growth.
5.6 Serving additional subscribers not anticipated
at the time of construction may be more of a problem in buried
plant than in aerial plant. Therefore, thorough planning is
of the utmost importance. Long range subscriber estimates
should be made prior to the preparation of the LD. The estimate
should take into account the upgrading of existing services
and the addition of new subscribers.
5.7 Local characteristics of the project area
should be thoroughly studied to determine whether normal or
extraordinary construction conditions exist before making
comparative cost studies. In addition, the determination should
be made as to whether special cable or wire shielding or other
protection methods would be required for rodent control so
that the increase in the incremental cost associated with
the rodent control protection methods can be evaluated.
5.8 For copper buried plant, the design should
provide for the optimum use of fine gauge cable (22 and 24
gauge conductors). Care should be exercised in the design
to ensure that transmission requirements will be met and that
high lightning areas are considered.
5.9 For copper buried plant, the choice of
the proper gauge conductors should depend on the transmission
and signaling requirements. Care should be exercised in selecting
the cables since initial cost differentials between the various
cable types, sizes, and conductor gauges can be appreciable.
Where economic costs indicate the use of digital carrier and
other types of electronic equipment over physical circuits,
the electronic equipment should be designed.
5.10 For optical fiber buried plant, the design
should provide for the use of either dispersion-unshifted
single mode fibers (operate at both the 1310 and 1550 nanometer
windows) or dispersion-shifted single mode fibers (operate
at the 1550 nanometer window). The choice as to which single
mode fiber to use should depend on the optical system's length
and the transmission and signaling requirements.
5.11 The design should be prepared in accordance
with the recommendations in RUS Bulletin 1751H-601, Lightwave
Fundamentals.
5.12 Economic and/or operating advantages
may often be realized by extending or reducing cable lengths
to eliminate splices or outside plant housings which may provide
savings in cable reel length purchases. Such considerations
should be made with careful evaluation of shield and/or armor
grounding requirements.
6. ECONOMIC CONSIDERATIONS
6.1 The decision to construct in a project
area using buried plant facilities should be based on an economic
analysis using the recommendations referenced in
RUS TE&CM Sections 218, Plant Annual Cost
Data for System Design Purposes and 219, Present Worth of
Annual Charge Studies for System Design.
6.2 If the economic analysis indicates that
the project area should be constructed using buried plant
facilities, a decision should then be made regarding the design
of the project area using either an all copper design or a
combination copper/fiber design.
6.3 Selection of either the all copper design
or the combination copper/fiber design should be based on
a ten-year economic plan, good engineering judgement and consideration
of the State Telecommunications Modernization Plan. The initial
and annual cost data should be used as economic guidelines
to supplement and support engineering judgements and decisions.
The objective is to choose the most suitable elements of the
new plant facilities. In general, the design with the lowest
annual cost should be selected. However, other considerations
such as reliability and quality of service, connecting company
arrangements, flexibility for meeting unforeseen conditions,
or other effects on system operation may outweigh annual cost
considerations.
6.4 Local characteristics of the project area
should be considered so that such factors as the adaptability
of the soil conditions to buried plant construction are known
before comparative cost studies are commenced. It should also
be determined if special types of equipment or cable are required
so that the added expense can be evaluated.
CLICK
HERE FOR PRINTABLE VERSION
|