| Specifications
for Filled Buried Wire (PE-86)
UNITED STATES DEPARTMENT OF
AGRICULTURE
Rural Electrification Administration
BULLETIN 1753F-206(PE-86)
SUBJECT: REA Specification for Filled Buried
Wires
TO: All Telephone Borrowers
REA Telephone Staff
EFFECTIVE DATE: December 20, 1993.
EXPIRATION DATE: Date of change in 7 CFR 1755.860
by rulemaking.
OFFICE OF PRIMARY INTEREST: Outside Plant
Branch, Telecommunications Standards Division.
PREVIOUS INSTRUCTIONS: This bulletin replaces
REA
Bulletin 345-86, REA Specification for Filled
Buried Service Wire, PE-86, issued October 7, 1982.
FILING INSTRUCTIONS: Discard REA Bulletin
345-86, REA Specification for Filled Buried Service Wire,
PE-86, dated October 7, 1982, and replace with this bulletin.
File with
7 CFR 1755 and on REANET.
PURPOSE: This specification covers REA requirements
for filled buried wires intended for direct burial as a subscriber
drop and/or distribution wire. This bulletin is a user friendly
guide and a reformat of the text codified in 7 CFR §1755.860
published at 58 FR 61002, dated November 19, 1993.
Every effort has been made to ensure the accuracy
of this document. However, in case of discrepancies, the regulations
at 7 CFR §1755.860 are the authorized
sources.
Wally Beyer 01/14/94
________________________________________ ___________________
Administrator Date
TABLE OF CONTENTS
1. Scope 7
2. Conductors and Conductor Insulation 7
3. Identification of Pairs and Twisting of
Pairs 11
4. Forming of the Wire Core 12
5. Filling Compound 12
6. Core Wrap (Optional) 13
7. Inner Jacket 13
8. Flooding Compound 14
9. Shield 14
10. Outer Jacket 16
11. Sheath Slitting Cord (Optional) 18
12. Identification Marker and Length Marker
18
13. Electric Requirements 20
14. Mechanical Requirements 22
15. Acceptance Testing and Extent of Testing
22
16. Summary of Records of Electrical and Physical
Tests 24
17. Manufacturing Irregularities 24
18. Preparation for Shipment 25
APPENDIX A: Qualifications Test Methods 27
APPENDIX B: Sheath Slitting Cord Qualification
39
APPENDIX C: Thermal Reel Wrap Qualification
40
INDEX:
Wire, Filled, Buried
CFR TO BULLETIN CONVERSION TABLE
7 CFR Bulletin 7 CFR Bulletin 7 CFR Bulletin
1755.860 1753F-206 1755.860 1753F-206 1755.860
1753F-206
(a) 1. (g)(1) 7.1 (m)(7) 13.7
(a)(1) 1.1 (g)(2) 7.2 (m)(8) 13.8
(a)(2) 1.2 (g)(3) 7.3 (m)(9) 13.9
(a)(3) 1.3 (g)(4) 7.4 (n) 14.
(a)(4) 1.4 (h) 8. (n)(1) 14.1
(b) 2. (h)(1) 8.1 (n)(2) 14.2
(b)(1) 2.1 (h)(2) 8.2 (n)(3) 14.3
(b)(2) 2.2 (h)(3) 8.3 (n)(4) 14.4
(b)(3) 2.3 (i) 9. (n)(5) 14.5
(b)(4) 2.4 (i)(1) 9.1 (o) 15.
(b)(5) 2.5 (i)(2) 9.2 (o)(1) 15.1
(b)(6) 2.6 (i)(3) 9.3 (o)(2) 15.2
(b)(7) 2.7 (i)(4) 9.4 (o)(3) 15.3
(b)(8) 2.8 (j) 10. (o)(4) 15.4
(b)(9) 2.9 (j)(1) 10.1 (o)(5) 15.5
(b)(10) 2.10 (j)(2) 10.2 (o)(6) 15.6
(b)(11) 2.11 (j)(3) 10.3 (p) 16.
(b)(12) 2.12 (j)(4) 10.4 (p)(1) 16.1
(c) 3. (j)(5) 10.5 (p)(2) 16.2
(c)(1) 3.1 (j)(6) 10.6 (q) 17.
(c)(2) 3.2 (j)(7) 10.7 (q)(1) 17.1
(c)(3) 3.3 (k) 11. (q)(2) 17.2
(c)(4) 3.4 (k)(1) 11.1 (r) 18.
(c)(5) 3.5 (k)(2) 11.2 (r)(1) 18.1
(c)(6) 3.6 (k)(3) 11.3 (r)(2) 18.2
(c)(7) 3.7 (l) 12. (r)(3) 18.3
(c)(8) 3.8 (l)(1) 12.1 (r)(4) 18.4
(c)(9) 3.9 (l)(2) 12.2 (r)(5) 18.5
(d) 4. (l)(3) 12.3 (r)(6) 18.6
(d)(1) 4.1 (l)(4) 12.4 (r)(7) 18.7
(d)(2) 4.2 (l)(5) 12.5 APPENDIX A APPENDIX
A
(d)(3) 4.3 (l)(6) 12.6 (I) 1.
(e) 5. (l)(7) 12.7 (II) 2.
(e)(1) 5.1 (l)(8) 12.8 (II)(1) 2.1
(e)(2) 5.2 (l)(9) 12.9 (II)(2) 2.2
(e)(3) 5.3 (l)(10) 12.10 (III) 3.
(e)(4) 5.4 (l)(11) 12.11 (III)(1) 3.1
(e)(5) 5.5 (m) 13. (III)(2) 3.2
(e)(6) 5.6 (m)(1) 13.1 (III)(3) 3.3
(f) 6. (m)(2) 13.2 (III)(4) 3.4
(f)(1) 6.1 (m)(3) 13.3 (III)(5) 3.5
(f)(2) 6.2 (m)(4) 13.4 (III)(6) 3.6
(f)(3) 6.3 (m)(5) 13.5 (III)(7) 3.7
(f)(4) 6.4 (m)(6) 13.6 (IV) 4.
(g) 7. (IV)(1) 4.1
(IV)(2) 4.2
(IV)(3) 4.3
(V) Formats
CFR TO BULLETIN CONVERSION TABLE
7 CFR Bulletin
1755.860 1753F-206
Appendix B Appendix B
(I) 1.
(II) 2.
(III) 3.
(III)(1) 3.1
(III)(2) 3.2
(III)(3) 3.3
(III)(4) 3.4
(III)(5) 3.5
Appendix C Appendix C
(I) 1.
(II) 2.
(III) 3.
(III)(1) 3.1
(III)(2) 3.2
(III)(3) 3.3
(III)(4) 3.4
(III)(5) 3.5
(III)(6) 3.6
(III)(7) 3.7
(III)(8) 3.8
ABBREVIATIONS
ANSI American National Standards Institute
ASTM American Society For Testing and Materials
AWG American Wire Gauge
°C Centigrade temperature scale
dc Direct current
dB/1000 ft Decibels per 1000 feet
dB/km Decibels per 1 kilometer
dB/mile Decibels per 1 mile
EIA Electronic Industries Association
Fo Known frequency
Fx New frequency
FEXT Far-end crosstalk
ft Feet
g Grams
HD High density polyethylene compound
IACS International Annealed Copper Standard
in. Inches
in./min Inches per 1 minute
Ko Known far-end crosstalk
Kx New far-end crosstalk
km Kilometer
kHz Kilohertz
kPa Kilopascals
kV Kilovolts
Lo Known length
Lx New length
lbf Pound force
lbf-ft Pound force-foot
LDHMW Low density, high molecular weight polyethylene
compound
LLDHMW Linear low density, high molecular
weight
polyethylene compound
m Meter
Max. Maximum
Min. Minimum
MD Medium density polyethylene compound
MHz Megahertz
micromhos/km Micromhos per 1 kilometer
MPa Megapascals
mm Millimeter
mm/min Millimeters per 1 minute
N Newton
N-m Newton-meter
nF/km Nanofarad per 1 kilometer
nF/mile Nanofarad per 1 mile
ohms-cm Ohms-centimeter
ohms/1000 ft Ohms per 1000 feet
pF/km Picofarads per 1 kilometer
pF/1000 ft Picofarads per 1000 feet
psi Pounds per square inch
psig Pounds per square inch gauge
REA Rural Electrification Administration
Yoc Open circuit admittance
Zsc Short circuit impedance
1. SCOPE
1.1 This specification covers the requirements
for filled
buried wires intended for direct burial as
a subscriber drop and/or distribution wire.
1.1.1 The conductors are solid copper, individually
insulated with an extruded solid insulating compound.
1.1.2 The insulated conductors are twisted
into pairs (a star-quad configuration is permitted for the
two pair wires) which are then stranded or oscillated to form
a cylindrical core.
1.1.3 A moisture resistant filling compound
is applied to the stranded conductors completely covering
the insulated conductors and filling the interstices between
the pairs.
1.1.4 The wire structure is completed by the
application of an optional core wrapping material, an inner
jacket, a flooding compound, a shield, a flooding compound
and an overall plastic jacket.
1.2 The number of pairs and gauge size of
conductors which are used within the REA program are provided
in the following table:
AWG 22 24
Pairs 2 2
3 3
1.3 All wires sold to REA borrowers for projects
involving
REA loan funds under this specification must
be accepted by
REA Technical Standards Committee "A"
(Telephone). For wires manufactured to this specification,
all design changes to an accepted design must be submitted
for acceptance. REA will
be the sole authority on what constitutes
a design change.
1.4 Materials, manufacturing techniques or
wire designs not specifically addressed by this specification
may be allowed
if accepted by REA. Justification for acceptance
of modified materials, manufacturing techniques or wire designs
must be provided to substantiate product utility and long
term stability and endurance.
2. CONDUCTORS AND CONDUCTOR INSULATION
2.1 Each conductor must be a solid round wire
of commercially pure annealed copper. Conductors must meet
the requirements
of ASTM B 3-90 except that requirements for
Dimensions and Permissible Variations are waived and elongation
requirements
are superseded by this specification.
2.2 The minimum conductor elongation in the
final wire must comply with the following limits when tested
in accordance with ASTM E 8-91.
Conductor - AWG Minimum Elongation - Percent
22 20
24 16
2.3 Joints made in conductors during the manufacturing
process may be brazed, using a silver alloy solder and nonacid
flux, or they may be welded using either an electrical or
cold welding technique. In joints made in uninsulated conductors,
the two conductor ends must be butted. Splices made in insulated
conductors need not be butted but may be joined in a manner
acceptable to REA.
2.4 The tensile strength of any section of
a conductor containing a factory joint must not be less than
85 percent
of the tensile strength of an adjacent section
of the solid conductor of equal length without a joint.
Engineering Information: The sizes of wire
used
and their nominal diameters shall be as shown
in
the following table:
AWG Nominal Diameter - mm (in.)
22 0.643 (0.0253)
24 0.511 (0.0201)
2.5 Each conductor must be insulated with
either a colored, solid, insulating grade, high density polyethylene
or crystalline propylene/ethylene copolymer or with a solid
natural primary layer and a colored, solid outer skin using
one of the insulating materials listed in Paragraphs 2.5.1
through 2.5.2 of this specification.
2.5.1 The polyethylene raw material selected
to meet the requirements of this specification must be Type
III,
Class A, Category 4 or 5, Grade E9 in accordance
with
ASTM D 1248-84(1989).
2.5.2 The crystalline propylene/ethylene raw
material selected to meet the requirements of this specification
must be
Class PP 200B 40003 E11 in accordance with
ASTM D 4101-82(1988).
2.5.3 Raw materials intended as conductor
insulation furnished to these requirements must be free from
dirt, metallic particles and other foreign matter.
2.5.4 All insulating raw materials must be
accepted by REA prior to their use.
2.6 All conductors in any single length of
wire must be insulated with the same type of material.
2.7 A permissible overall performance level
of faults in conductor insulation must average not greater
than one fault per 12,000 conductor meters (40,000 conductor
ft) for each gauge of conductor.
2.7.1 All insulated conductors must be continuously
tested for insulation faults during the twinning operation
with the method of test acceptable to REA. The length count
and number of faults must be recorded. The information must
be retained for a period of 6 months and be available for
review by REA when requested.
2.7.2 The voltages for determining compliance
with the requirements of Paragraph 2.7, are as follows:
AWG DC Voltages (kV)
22 6.0
24 5.0
2.8 Repairs to the conductor insulation during
manufacturing are permissible. The method of repair must be
accepted by REA prior to its use. The repaired insulation
must be capable of meeting the relevant electrical requirements
of this specification.
2.9 All repaired sections of insulation must
be retested in the same manner as originally tested for compliance
with the requirements of Paragraph 2.7 of this specification.
2.10 Colored insulating material removed from
or tested on the conductor, from a finished wire, must be
capable of meeting the following performance requirements.
Crystalline
Propylene/Ethylene
Property Polyethylene Copolymer
Melt Flow Rate
Percent increase
from raw material,
Maximum
<0.5 (Initial 50 --
Melt Index)
0.5-2.00 (Initial 25 --
Melt Index)
<5.0 (Initial Melt -- 110
Index)
Tensile Strength
Minimum, MPa (psi) 16.5 (2,400) 21.0 (3,000)
Ultimate Elongation
Minimum, Percent 300 300
Cold Bend
Failures, Maximum 0/10 0/10
Shrinkback
Maximum, mm (in.) 10 (0.375) 10 (0.375)
Oxygen Induction Time
Minimum, Minutes 20 20
2.11 Testing Procedures: The procedures for
testing the insulation samples for compliance with Paragraph
2.10 of this specification must be as follows.
2.11.1 Melt Flow Rate: The melt flow rate
must be determined
as described in ASTM D 1238-90b. Condition
E must be used for polyethylene. Condition L shall be used
for crystalline propylene/ethylene copolymer. The melt flow
test must be conducted prior to the filling operation.
2.11.2 Tensile Strength and Ultimate Elongation:
Samples of
the insulation material, removed from the
conductor, must be tested in accordance with ASTM D 4565-90a
using the following conditions. The minimum length of unclamped
specimen must be
50 mm (2.0 in.). The minimum speed of jaw
separation must be
25 mm (1.0 in.) per minute per 25 mm (1.0
in.) of unclamped specimen. The temperature of specimens and
surrounding must be 23 + 1°C.
Note: Quality assurance testing at a jaw separation
speed of 500 mm/min (20 in./min) is permissible. Failures
at this rate must be retested at the 50 mm/min (2 in./min)
rate to determine specification compliance.
2.11.3 Cold Bend: Samples of the insulation
material on the conductor must be tested in accordance with
ASTM D 4565-90a at
a temperature of -40 + 1°C with a mandrel
diameter equal to
3 times the outside diameter of the insulated
conductor. There must be no cracks visible to normal or corrected-to-normal
vision.
2.11.4 Shrinkback: Samples of insulation must
be tested for four hours in accordance with ASTM D 4565-90a.
The temperature for the type of material is as follows:
Material Temperature
Polyethylene 115 + 1°C
Crystalline
Propylene/Ethylene 130 + 1°C
Copolymer
2.11.5 Oxygen Induction Time: Samples of insulation,
which
have been conditioned in accordance with Paragraph
17.3 of
ASTM D 4565-90a, must be tested in accordance
with the procedures of ASTM D 4565-90a using copper pans and
a test temperature of
199 + 1°C.
2.12 Other methods of testing may be used
if acceptable to REA.
3. IDENTIFICATION OF PAIRS AND TWISTING OF
PAIRS
3.1 The insulation must be colored to identify:
a. The tip and ring conductor of each pair,
and
b. Each pair in the completed wire.
3.2 The colors to be used to provide identification
of the tip and ring conductor of each pair are shown in the
following table:
Pair Color
No. Tip Ring
1 White Blue
2 White Orange
3 White Green
3.3 Standards of Color: The colors of the
insulated conductors supplied in accordance with this specification
are specified in terms of the Munsell Color System (ASTM D
1535-89) and must comply with the "Table of Wire and
Cable Limit Chips" as defined in ANSI/EIA-359-A-84. (Visual
color standards meeting these requirements may be obtained
directly from the Munsell Color
Company, Inc., 2441 North Calvert Street,
Baltimore, Maryland 21218).
3.4 Positive identification of the tip and
ring conductors of each pair by marking each conductor of
a pair with the color of its mate is permissible. The method
of marking must be accepted by REA prior to its use.
3.5 Other methods of providing positive identification
of the tip and ring conductors of each pair may be employed
if accepted by REA prior to its use.
3.6 The insulated conductors must be twisted
into pairs.
3.7 In order to provide sufficiently high
crosstalk isolation, the pair twists must be designed to enable
the wire to meet the
capacitance unbalance and the crosstalk loss
requirements of Paragraphs 13.2, 13.3, and 13.4 of this specification.
3.8 The average length of pair twists in any
pair in the finished wire, when measured on any 3 m (10 ft)
length, must not exceed 152 mm (6 in.).
3.9 An alternative method of forming the two-pair
wire is the use of a star-quad configuration.
3.9.1 The assembly of the star-quad must be
such as to enable the wire to meet the capacitance unbalance
and the crosstalk
loss requirements of Paragraphs 13.2, 13.3,
and 13.4 of this specification.
3.9.2 The four individual insulated conductors
must be twisted together to form a star-quad configuration
with the tip and ring conductors of each pair diagonally opposite
each other in the quad.
3.9.3 The average length of twist for the
star-quad in the finished wire, when measured on any 3 m (10
ft) length, must
not exceed 152 mm (6 in.).
3.9.4 The following color scheme must be used
to provide identification of the tip and ring conductor of
each pair
in the star-quad:
Color
Pair No. Tip Ring
1 White with blue stripe Blue
2 White with orange stripe Orange
3.9.5 If desired, the blue and orange conductors
may contain a white stripe. The stripes in this case must
be narrow enough so that the tip and ring identification is
obvious.
4. FORMING OF THE WIRE CORE
4.1 Twisted pairs or star-quad configuration
must be assembled in such a way as to form a substantially
cylindrical group.
4.2 The filling compound must be applied to
the wire core in such a way as to provide a completely filled
core as is commercially practical.
4.3 If desired for manufacturing reasons,
white or colored binders of nonhygroscopic and nonwicking
material may be applied over the core.
5. FILLING COMPOUND
5.1 After or during the stranding operation
and prior to application of the optional core wrap and inner
jacket, a homogeneous filling compound free of agglomerates
must be
applied to the wire core. The compound must
be as nearly colorless as is commercially feasible and consistent
with
the end product requirements and pair identification.
5.2 The filling compound must be free from
dirt, metallic particles and other foreign matter. It must
be applied in
such a way as to fill the space within the
wire core.
5.3 The filling compound must be nontoxic
and present no dermal hazards.
5.4 The filling compound must exhibit the
following dielectric properties at a temperature of 23 + 3°C
when measured in accordance with ASTM D 150-87 or ASTM D 4872-88.
5.4.1 The dissipation factor must not exceed
0.0015 at a frequency of 1 MHz.
5.4.2 The dielectric constant must not exceed
2.30.
5.5 The volume resistivity must not be less
than 1012 ohm-cm
at a temperature of 23 + 3°C when measured
in accordance with
ASTM D 257-91 or ASTM D 4872-88.
5.6 The individual wire manufacturer must
satisfy REA that the filling compound selected for use is
suitable for its intended application. The filling compound
must be compatible with the wire components when tested in
accordance with ASTM D 4568-86 at a temperature of 80°C.
6. CORE WRAP (OPTIONAL)
6.1 When a core wrap tape is used, it must
consist of a layer of nonhygroscopic and nonwicking dielectric
material. The wrap must be applied with an overlap.
6.2 The core wrap must provide a sufficient
heat barrier to prevent visible evidence of conductor insulation
deformation or adhesion between conductors, caused by adverse
heat transfer during the inner jacketing operation.
6.3 If required for manufacturing reasons,
white or colored binders of nonhygroscopic and nonwicking
material may be applied over the core wrap.
6.4 Sufficient filling compound must be applied
to the core wrap that voids or air spaces existing between
the core and inner side of the core wrap are minimized.
7. INNER JACKET
7.1 An inner jacket must be applied over the
core and/or core wrap.
7.2 The jacket must be free from holes, splits,
blisters, or other imperfections and must be as smooth and
concentric as is consistent with the best commercial practice.
7.3 The inner jacket material and test requirements
must be
as specified for the outer jacket material
per Paragraphs 10.3 through 10.5.4 of this specification.
7.4 The inner jacket thickness at any point
must not be less than 0.5 mm (0.020 in.). The thickness must
be determined
from measurements on 50 mm (2 in.) samples
taken not less than 0.3 m (1 ft) from either end of the wire.
The average must be
determined from 4 readings taken approximately
90° apart on any cross section of the samples. The maximum
and minimum points must be determined by exploratory measurements.
The maximum thickness minus the minimum thickness at any cross
section must not exceed 43 percent of the average thickness
at that cross section.
8. FLOODING COMPOUND
8.1 Sufficient flooding compound must be applied
on all sheath interfaces so that voids and air spaces in these
areas are minimized.
8.2 The flooding compound must be compatible
with the jacket when tested in accordance with ASTM D 4568-86
at a temperature of 80°C. The floodant must exhibit adhesive
properties sufficient to prevent jacket slip when tested in
accordance with the requirements of Appendix A, Paragraph
3.5, of this specification.
8.3 The individual wire manufacturer must
satisfy REA that the flooding compound selected for use is
acceptable for the application.
9. SHIELD
9.1 A shield must be applied either longitudinally
or helically over the inner jacket.
9.1.1 If the shield is applied longitudinally,
it must be corrugated.
9.1.2 If the shield is applied helically,
it must be smooth.
9.2 The overlap for longitudinally applied
shields must be a minimum of 2 mm (0.075 in.) The overlap
for helically applied shields must be a minimum of 23 percent
of the tape width.
9.3 General requirements for application of
the shielding material are as follows:
9.3.1 Successive lengths of shielding tapes
may be joined during the manufacturing process by means of
cold weld, electric weld, soldering with a nonacid flux or
other acceptable means.
9.3.2 Where two ends of a metal shield are
to be joined together, care shall be taken to clean the metal
surfaces in order to provide for a good mechanical and electrical
connection.
9.3.3 The shields of each length of wire must
be tested for continuity. A one meter (3 ft) section of shield
containing a factory joint must exhibit not more than 110
percent of the resistance of a shield of equal length without
a joint.
9.3.4 The breaking strength of any section
of a shield tape containing a factory joint must not be less
than 80 percent of the breaking strength of an adjacent section
of the shield of equal length without a joint.
9.3.5 The reduction in thickness of the shielding
material due to the corrugating or application process must
be kept to a minimum and must not exceed 10 percent at any
spot.
9.3.6 The shielding material must be applied
in such a manner
as to enable the wire to pass the bend test
as specified in Paragraph 14.3 of this specification.
9.4 The following materials are acceptable
for use as wire shielding.
Standard Wire Gopher Resistant Wire
Copper Alloy 220 (Bronze) Copper-Clad Stainless
Steel
0.1016 + 0.0076 mm 0.1270 + 0.0127 mm
(0.0040 + 0.0003 in. (0.0050 + 0.0005 in.)
Copper Alloy 220 (Bronze) Copper Alloy 664
0.1270 + 0.0127 mm 0.1397 + 0.0127 mm
(0.0050 + 0.0005 in.) (0.0055 + 0.0005 in.)
Copper-Clad Alloy Steel
0.1270 + 0.0127 mm
(0.0050 + 0.0005 in.)
9.4.1 The copper-clad steels and copper alloy
664 shielding
tapes must be capable of meeting the following
performance requirements prior to application to the wire:
Property Requirement
Tensile Strength
Minimum, MPa (psi) 379 (55,000)
Tensile Yield
Minimum, MPa (psi) 241 (35,000)
Elongation
Minimum, percent in 15
50 mm (2 in.)
9.4.2 Copper Alloy 220: The shielding material,
prior to application to the wire, must be in the fully annealed
condition and must conform to the requirements of ASTM B 694-86
for C22000 commercial bronze.
9.4.3 Copper-Clad Stainless Steel: In addition
to meeting the requirements of Paragraph 9.4.1 of this specification,
the shielding material, prior to application to the wire,
must be in the fully annealed condition and must conform to
the requirements
of ASTM B 694-86, with a cladding ratio of
16/68/16 and must have a minimum electrical conductivity of
28 percent IACS when measured in accordance with ASTM B 193-87.
9.4.4 Copper Alloy 664: In addition to meeting
the requirements of Paragraph 9.4.1 of this specification,
the shielding material, prior to application to the wire,
must be annealed temper and must conform to the requirements
of ASTM B 694-86 and must have a minimum electrical conductivity
of 28 percent IACS when measured in accordance with ASTM B
193-87.
9.4.5 Copper-Clad Alloy Steel: In addition
to meeting the requirements of Paragraph 9.4.1 of this specification,
the shielding material, prior to application to the wire,
must be
in the fully annealed condition and the copper
component must conform to the requirements of ASTM B 224-91
and the alloy steel component must conform to the requirements
of ASTM A 505-87, with a cladding ratio of 16/68/16, and must
have a minimum electrical conductivity of 28 percent IACS
when measured in accordance with ASTM B 193-87.
10. OUTER JACKET
10.1 The outer jacket must provide the wire
with a tough, flexible, protective covering which can withstand
exposure to sunlight, to atmospheric temperatures and stresses
reasonably expected in normal installation and service.
10.2 The jacket must be free from holes, splits,
blisters, or other imperfections and must be as smooth and
concentric as is consistent with the best commercial practice.
10.3 The raw material used for the outer jacket
must be one of the five types listed in Paragraphs 10.3.1
through 10.3.5 of this specification. The raw material must
contain an antioxidant to provide long term stabilization
and the materials must contain a 2.60 + 0.25 percent concentration
of furnace black to provide ultraviolet shielding. Both the
antioxidant and furnace black must be compounded into the
material by the raw material supplier.
10.3.1 Low density, high molecular weight
polyethylene (LDHMW) must conform to the requirements of ASTM
D 1248-84(1989), Type I, Class C, Category 4 or 5, Grade J3.
10.3.2 Low density, high molecular weight
ethylene copolymer (LDHMW) must conform to the requirements
of ASTM D 1248-84 (1989), Type I, Class C, Category 4 or 5,
Grade J3.
10.3.3 Linear low density, high molecular
weight polyethylene (LLDHMW) must conform to the requirements
of ASTM D 1248-84 (1989), Type I, Class C, Category 4 or 5,
Grade J3.
10.3.4 High density polyethylene (HD) must
conform to the requirements of ASTM D 1248-84(1989), Type
III, Class C,
Category 4 or 5, Grade J4.
10.3.5 Medium density polyethylene (MD) must
conform to
the requirements of ASTM D 1248-84(1989),
Type II, Class C, Category 4 or 5, Grade J4.
10.3.6 Particle size of the carbon selected
for use must not average greater than 20 nanometers.
10.3.7 Absorption coefficient must be a minimum
of 400 in accordance with the procedures of ASTM D 3349-86.
10.4 The outer jacketing material removed
from or tested on
the wire must be capable of meeting the following
performance requirements:
LLDHMW,
Ethylene LDHMW HD or MD
Property Copolymer Polyethylene Polyethylene
Melt Flow Rate
Percent increase
from raw material
Maximum 50 50
<0.41 (Initial
Melt Index) 100 -- --
0.41 - 2.00
(Initial Melt
Index) 50 -- --
Tensile Strength
Minimum, MPa (psi) 12.0 (1,700) 12.0 (1,700)
16.5 (2,400)
Ultimate Elongation
Percent, Minimum 400 400 300
Shrinkback
Percent of Length,
Maximum 5 5 5
Impact
Failures, Maximum 2/10 2/10 2/10
10.5 Testing Procedures: The procedures for
testing the jacket samples for compliance with Paragraph 10.4
of this specification must be as follows.
10.5.1 Melt Flow Rate: The melt flow rate
must be as determined by ASTM D 1238-90b, Condition E. Jacketing
material must be free from flooding and filling compound.
10.5.2 Tensile Strength and Ultimate Elongation:
Test in accordance with ASTM D 4565-90a, using a jaw separation
speed
of 500 mm/min (20 in./min) for low density
material and
50 mm/min (2 in./min) for high and medium
density materials.
10.5.3 Shrinkback: Test in accordance with
the procedures specified in ASTM D 4565-90a using a test temperature
of
100 + 1°C for low density material and
a test temperature
of 115 + 1°C for high and medium density
materials.
10.5.4 Impact: The test must be performed
in accordance with ASTM D 4565-90a using an impact force of
4 N-m (3 lbf-ft) at a temperature of -20 + 2°C. The cylinder
must strike the sample at the shield overlap. A crack or split
in the jacket constitutes failure.
10.6 Jacket Thickness: The minimum jacket
thickness must be 0.64 mm (0.025 in.) except that the minimum
thickness over the sheath slitting cord, if present, must
be 0.46 mm (0.018 in.). The minimum point must be determined
by exploratory measure-ments. The average thickness at any
cross section must be determined from four readings including
the minimum point, taken approximately 90° apart. The
thickness measurement must exclude any jacket material that
has formed into the corrugation. The maximum thickness at
any cross section must not be greater than 155 percent of
the minimum thickness.
10.7 Eccentricity: The eccentricity of the
jacket must not exceed 43 percent when calculated using the
formula as follows:
Max. Thickness - Min. Thickness x 100 Percent
Average Thickness
11. SHEATH SLITTING CORD (OPTIONAL)
11.1 Sheath slitting cords may be used in
the wire structure at the option of the manufacturer.
11.2 When a sheath slitting cord is used it
must be non-hygroscopic and nonwicking, continuous throughout
a length
of wire, and of sufficient strength to open
the sheath without breaking the cord.
11.3 Sheath slittings cords must be capable
of consistently slitting the jacket(s) and/or shield for a
continuous length
of 0.6 m (2 ft) when tested in accordance
with the procedure specified in Appendix B of this specification.
12. IDENTIFICATION MARKER AND LENGTH MARKER
12.1 Each length of wire must be permanently
identified as to manufacturer and year of manufacture.
12.2 The number of conductor pairs and their
gauge size must be marked on the jacket.
12.3 The marking must be printed on the jacket
at regular intervals of not more than 1.5 m (5 ft).
12.4 An alternative method of marking may
be used if accepted by REA prior to its use.
12.5 The completed wire must have sequentially
numbered length markers in FEET OR METERS at regular intervals
of not more than 1.5 m (5 ft) along the outside of the jacket.
12.6 The method of length marking must be
such that for any single length of wire, continuous sequential
numbering must be employed.
12.7 The numbers must be dimensioned and spaced
to produce good legibility and must be approximately 3 mm
(0.125 in.) in height. An occasional illegible marking is
permissible if there is a legible marking located not more
than 1.5 m (5 ft) from it.
12.8 The method of marking must be by means
of suitable surface markings producing a clear distinguishable
contrasting marking acceptable to REA. Where direct or transverse
printing is employed, the characters should be indented to
produce greater durability of marking. Any other method of
length marking must be acceptable to REA as producing a marker
suitable for the field. Size, shape and spacing of numbers,
durability and overall legibility of the marker will be considered
in acceptance of the method.
12.9 The accuracy of the length marking must
be such that the actual length of any wire section is never
less than the length indicated by the marking and never more
than one percent greater than the length indicated by the
marking.
12.10 The color of the initial marking must
be white or silver. If the initial marking fails to meet the
requirements of the preceding paragraphs, it will be permissible
to either remove
the defective marking and re-marking with
the white or silver color or leave the defective marking on
the wire and re-mark
with yellow. No further re-marking is permitted.
Any re-marking must be on a different portion of the wire
circumference than
any existing marking when possible and have
a numbering sequence differing from any other existing marking
by at least 5,000.
12.11 Any reel of wire which contains more
than one set of sequential markings must be labeled to indicate
the color and sequence of marking to be used. The labeling
must be applied
to the reel and also to the wire.
13. ELECTRICAL REQUIREMENTS
13.1. Mutual Capacitance And Conductance:
13.1.1 The average mutual capacitance (corrected
for length)
of all pairs in any reel must not exceed 52
+ 4 nF/km (83 +
7 nF/mile) when tested in accordance with
ASTM D 4566-90 at
a frequency of 1.0 + 0.1 kHz and a temperature
of 23 + 3°C.
13.1.2 The mutual conductance (corrected for
length and gauge)
of any pair must not exceed 2 micromhos/km
(3.3 micromhos/mile) when tested in accordance with ASTM D
4566-90 at a frequency of 1.0 + 0.1 kHz and a temperature
of 23 + 3°C.
13.2 Pair-to-Pair Capacitance Unbalance: The
capacitance unbalance between any pair of the completed wire
must not
exceed 145 pF/km (80 pF/1000 ft) when tested
in accordance with ASTM D 4566-90 at a frequency of 1.0 +
0.1 kHz and a temperature of 23 + 3°C.
13.3 Pair-to-Ground Capacitance Unbalance:
13.3.1 Pair-to-Ground: The capacitance unbalance
as measured on the individual pairs of the completed wire
must not exceed
2625 pF/km (800 pF/1000 ft) when tested in
accordance with
ASTM D 4566-90 at a frequency of 1.0 + 0.1
kHz and a temperature of 23 + 3°C.
13.3.2 When measuring pair-to-ground capacitance
unbalance all pairs except the pair under test are grounded
to the shield.
13.3.3 Pair-to-ground capacitance unbalance
may vary directly with the length of the wire.
13.4 Far-End Crosstalk Loss: The output-to-output
far-end crosstalk loss between any pair combination of a completed
wire when measured in accordance with ASTM D 4566-90 at a
test frequency of 150 kHz must not be less than 58 dB/km (63
dB/1000 ft). If the loss Ko at a frequency Fo for length Lo
is known, then Kx can be determined for any other frequency
Fx or length
Lx by:
Fx Lx
FEXT loss (Kx) = Ko -20 log10 -- -10 log10
--
Fo Lo
13.5 Attenuation: The attenuation of any individual
pair on any reel of wire must not exceed the following limits
when measured at or corrected to a temperature of 20 + 1°C
and a test frequency of 150 kHz. The test must be conducted
in accordance with
ASTM D 4566-90.
Individual Pair Attenuation
dB/km (dB/mile)
Conductor
AWG Maximum Minimum
22 6.8 (11.0) 5.0 (8.1)
24 8.7 (14.0) 6.6 (10.7)
13.6 Insulation Resistance: Each insulated
conductor in each length of completed wire, when measured
with all other insulated conductors and the shield grounded,
must have an insulation resistance of not less than 1600 megohm-kilometer
(1000 Megohm-mile) at 20 + 1°C. The measurement must be
made in accordance with the procedures of ASTM D 4566-90.
13.7 High Voltage Test:
13.7.1 In each length of completed wire, the
insulation between conductors when tested in accordance with
ASTM D 4566-90 must withstand for 3 seconds a dc potential
whose value is not less than:
a. 5.0 kV for 22-gauge conductors, and
b. 4.0 kV for 24-gauge conductors.
13.7.2 In each length of completed wire, the
dielectric strength between the shield and all conductors
in the core must be tested in accordance with ASTM D 4566-90
and must withstand, for
3 seconds, a dc potential whose value is not
less than 20 kV.
13.8 Conductor Resistance: The dc resistance
of any conductor must be measured in the completed wire in
accordance with ASTM D 4566-90 and must not exceed the following
values when measured at or corrected to a temperature of 20
+ 1°C.
Maximum Resistance
AWG ohms/kilometer (ohms/1000 ft)
22 57.1 (17.4)
24 90.2 (27.5)
13.9 Resistance Unbalance:
13.9.1 The difference in dc resistance between
the two conductors of any pair in the completed wire must
not exceed
5.0 percent when measured in accordance with
the procedures of ASTM D 4566-90.
13.9.2 The resistance unbalance between tip
and ring conductors shall be random with respect to the direction
of unbalance.
That is, the resistance of the tip conductors
shall not be consistently higher with respect to the ring
conductors and
vice versa.
14. MECHANICAL REQUIREMENTS
14.1 Defective Wire: Pairs in each length
of wire will not be permitted to have either a ground, cross,
short or open circuit condition.
14.2 Wire Breaking Strength: The breaking
strength of the completed wire must not be less than 890 N
(200 lbf) when tested in accordance with ASTM D 4565-90a using
a jaw separation speed of 25 mm/min (1.0 in./min).
14.3 Wire Bending Test: The completed wire
must be capable of meeting the requirements of ASTM D 4565-90a
after conditioning at -20 + 2°C and at 23 ± 2°C.
14.4 Water Penetration Test:
14.4.1 A one meter (3 ft) length of completed
wire must be stabilized at 23 + 2°C and tested in accordance
with
ASTM D 4565-90a using a one meter (3 ft) water
head over the sample or placed under the equivalent continuous
pressure for
one hour.
14.4.2 After the one hour period, there must
be no water leakage in the sheath interfaces, under the core
wrap or between any insulated conductors in the core.
14.4.3 If water leakage is detected in the
first sample, one
3 m (10 ft) additional adjacent sample from
the same reel of
wire shall be tested in accordance with Paragraph
14.4.2 of this specification. If the second sample exhibits
water leakage, the entire reel of wire is to be rejected.
If the second sample exhibits no leakage, the entire reel
of wire is considered acceptable.
14.5 Compound Flow Test: The completed wire
must be capable of meeting the compound flow test specified
in ASTM D 4565-90a when exposed for a period of 24 hours at
a temperature of 80 + 1°C. At the end of this test period,
there must be no evidence of flowing or dripping of compound
from either the core or sheath interfaces.
15. ACCEPTANCE TESTING AND EXTENT OF TESTING
15.1 The tests described in Appendix A of
this specification are intended for acceptance of wire designs
and major modifications of accepted designs. REA decides what
constitutes a major modification. These tests are intended
to show the inherent capability of the manufacturer to produce
wire products having long life and stability.
15.2 For initial acceptance, the manufacturer
must submit:
a. An original signature certification that
the product
fully complies with each section of this specification;
b. Qualification Test Data, per Appendix A
of this
specification;
c. To periodic plant inspections;
d. A certification that the product does or
does not comply
with the domestic origin manufacturing provisions
of the
"Buy American" requirements of the
Rural Electrification
Act of 1938 (7 U.S.C. 901 et seq.);
e. Written user testimonials concerning performance
of the
product; and
d. Other nonproprietary data deemed necessary
by the Chief,
Outside Plant Branch (Telephone).
15.3 For requalification acceptance, the manufacturer
must submit an original signature certification that the product
fully complies with each section of the specification,
excluding the Qualification Section, and a certification that
the product does or does not comply with the domestic origin
manufacturing provisions of the "Buy American" requirements
of the Rural Electrification Act of 1938 (7 U.S.C. 901 et
seq.) for acceptance by June 30 every three years. The required
data
and certification must have been gathered
within 90 days of
the submission.
15.4 Initial and requalification acceptance
requests should be addressed to:
Chairman, Technical Standards
Committee "A" (Telephone)
Telecommunications Standards Division
Rural Electrification Administration
Washington, D.C. 20250-1500
15.5 Tests on 100 percent of completed wire:
15.5.1 The shield of each length of wire must
be tested for continuity using the procedures of ASTM D 4566-90.
15.5.2 Dielectric strength between all conductors
and the shield must be tested to determine freedom from grounds
in accordance with Paragraph 13.7.2 of this specification.
15.5.3 Each conductor in the completed wire
must be tested for continuity using the procedures of ASTM
D 4566-90.
15.5.4 Dielectric strength between conductors
must be tested
to ensure freedom from shorts and crosses
in accordance with Paragraph 13.7.1 of this specification.
15.5.5 The average mutual capacitance must
be measured on all wires.
15.6 Capability Tests: Tests on a quality
assurance basis must be made as frequently as is required
for each manufacturer to determine and maintain compliance
with:
15.6.1 Performance requirements for conductor
insulation and
jacket material;
15.6.2 Performance requirements for filling
and flooding
compounds;
15.6.3 Sequential marking and lettering;
15.6.4 Capacitance unbalance and crosstalk;
15.6.5 Insulation resistance;
15.6.6 Conductor resistance and resistance
unbalance;
15.6.7 Wire bending and wire breaking strength
tests;
15.6.8 Mutual conductance and attenuation;
and
15.6.9 Water penetration and compound flow
tests.
16. SUMMARY OF RECORDS OF ELECTRICAL AND PHYSICAL
TESTS
16.1 Each manufacturer must maintain suitable
summary of records for a period of at least 3 years for all
electrical and physical tests required on completed wire by
this specification as specified in Paragraphs 15.5 and 15.6
of this specification. The test data for a particular reel
shall be in a form that it may be readily available to the
purchaser or to REA upon request.
16.2 Measurements and computed values must
be rounded off to the number of places of figures specified
for the requirement according to ASTM E 29-90.
17. MANUFACTURING IRREGULARITIES
17.1 Repairs to the inner jacket and shield
are not permitted in wire supplied to the end user under this
specification.
17.2 Minor defects in the outer jackets (defects
having a dimension of 3 mm (0.125 in.) or less in any direction)
may
be repaired by means of heat fusing in accordance
with good commercial practices utilizing sheath grade compound.
18. PREPARATION FOR SHIPMENT
18.1 The wire must be shipped on reels. The
diameter of the drum must be large enough to prevent damage
to the wire from reeling or unreeling. The reels must be substantial
and so constructed as to prevent damage to the wire during
shipment
and handling.
18.2 The thermal wrap must comply with the
requirements of Appendix C of this specification. When a thermal
reel wrap
is supplied, the wrap must be applied to the
reel and must be suitably secured in place to minimize thermal
exposure to the wire during storage and shipment. The use
of the thermal reel wrap as an means of reel protection will
be at the option of
the manufacturer unless specified by the end
user.
18.3 The outer end of the wire must be securely
fastened to
the reel head so as to prevent the wire from
becoming loose in transit. The inner end of the wire must
be securely fastened
in such a way as to make it readily available
if required for electrical testing. Spikes, staples, or other
fastening devices which penetrate the wire jacket must not
be used. The method of fastening the wire ends must be accepted
by REA prior to it being used.
18.4 Each length of wire must be wound on
a separate reel unless otherwise specified or agreed to by
the purchaser.
18.5 Each reel must be plainly marked to indicate
the direction in which it should be rolled to prevent loosening
of the wire on the reel.
18.6 Each reel must be stenciled or labeled
on either one
or both sides with the name of the manufacturer,
year of manufacture, actual shipping length, an inner and
outer end sequential length marking, description of the wire,
reel number and the REA wire designation.
WIRE DESIGNATION
BFW...
Wire Construction...
Pair Count...
Conductor Gauge...
N = Copper Alloy 220 (Bronze) Shield
Y = Gopher Resistant Shields
Example: BFWY 3-24
Buried Filled Wire, Gopher Resistant Shield,
3 pair, 24 AWG
18.7 Both ends of the filled buried wire,
manufactured to the requirements of this specification, must
be equipped with end caps which are acceptable to REA.
(The information and recordkeeping requirements
of this specification have been approved by the Office of
Management
and Budget (0MB) under Control Number 0572-0077).
UNITED STATES DEPARTMENT OF AGRICULTURE
Rural Electrification Administration
APPENDIX A
FILLED BURIED WIRE
Qualifications Test Methods Bulletin 1753F-206(PE-86)
1. The test procedures described in this appendix
are for qualification of initial designs and major modifications
of "accepted" designs. Included in Paragraph 5 of
this appendix
are suggested formats that may be used in
submitting test results to REA.
2. SAMPLE SELECTION AND PREPARATION
2.1 All testing must be performed on lengths
removed sequentially from the same 3 pair, 22 gauge jacketed
wire.
This wire must not have been exposed to temperatures
in excess
of 38°C since its initial cool down after
sheathing. The lengths specified are minimum lengths and if
desirable from a laboratory testing standpoint longer lengths
may be used.
2.1.1 Length A shall be 10 + 0.2 m (33 + 0.5
ft) long and must be maintained at 23 + 3°C. One length
is required.
2.1.2 Length B shall be 12 + 0.2 m (40 + 0.5
ft) long. Prepare the test sample by removing the inner and
outer jacket, shield and core wrap, if present, for a sufficient
distance on both ends to allow the insulated conductors to
be flared out. Remove sufficient conductor insulation so that
appropriate electrical test connections can be made at both
ends. Coil the specimen with a diameter of 15 to 20 times
its sheath diameter. Three lengths are required.
2.1.3 Length C shall be one meter (3 ft) long.
Four lengths are required.
2.1.4 Length D shall be 300 mm (1 ft) long.
Four lengths are required.
2.1.5 Length E shall be 600 mm (2 ft) long.
Four lengths are required.
2.1.6 Length F shall be 3 m (10 ft) long and
must maintained at 23 + 3°C for the duration of the test.
Two lengths are required.
2.2 Data Reference Temperature: Unless otherwise
specified, all measurements shall be made at 23 + 3°C.
3. ENVIRONMENTAL TESTS
3.1 Heat Aging Test
3.1.1 Test Samples: Place one sample each
of lengths B, C, D, and E in an oven or environmental chamber.
The ends of sample B must exit from the chamber or oven for
electrical tests. Securely seal the oven exit holes.
3.1.2 Sequence of Tests: After conditioning
the samples are to be subjected to the following tests:
a. Water Immersion Test outlined in Paragraph
3.2 of
this appendix.
b. Water Penetration Test outlined in Paragraph
3.3 of
this appendix.
c. Insulation Compression Test outlined in
Paragraph 3.4 of this appendix.
d. Jacket Slip Strength Test outlined in Paragraph
3.5
of this appendix.
3.1.3 Initial Measurements
3.1.3.1 For sample B, measure the open circuit
capacitance and conductance for each pair at 1 and 150 kHz
and the attenuation at 150 kHz after conditioning the sample
at the data reference temperature for 24 hours. Calculate
the average and standard deviation for the data of the 3 pairs
on a per kilometer (per mile) basis.
3.1.3.2 The attenuation at 150 kHz may be
calculated from
Yoc and Zsc or may be obtained by direct measurement
of attenuation.
3.1.3.3 Record on suggested formats attached
in Paragraph 5 of this appendix or on other easily readable
formats.
3.1.4 Heat Conditioning
3.1.4.1 Immediately after completing the initial
measurements, condition the sample for 14 days at a temperature
of 65 + 2°C.
3.1.4.2 At the end of this period note any
exudation of filling compounds. Measure and calculate the
parameters given in Paragraph 3.1.3 of this appendix. Record
on suggested formats in Paragraph 5 of this appendix or on
other easily readable formats.
3.1.4.3 Cut away and discard a one meter (3
ft) section from each end of length B.
3.1.5 Overall Electrical Deviation
3.1.5.1 Calculate the percent change in all
average parameters between the final parameters after conditioning
with the initial parameters in Paragraph 3.1.3 of this appendix.
3.1.5.2 The stability of the electrical parameters
after completion of the test must be within the following
prescribed limits:
a. Capacitance: The average mutual capacitance
must be within 5 percent of its original value;
b. The change in average mutual capacitance
must
be less than 5 percent over the frequency
range
of 1 to 150 kHz;
c. Conductance: The average mutual conductance
must not exceed 2 micromhos/kilometer
(3.3 micromhos/mile) at a frequency of 1 kHz;
and
d. Attenuation: The attenuation must not have
increased by more than 5 percent over its
original
value.
3.2 Water Immersion Electrical Test
3.2.1 Test Sample Selection: The 10 m (33
ft) section of length B must be tested.
3.2.2 Test Sample Preparation: Prepare the
sample by removing the inner and outer jacket, shield, and
core wrap, if present, for a sufficient distance to allow
one end to be accessed for test connections. Cut out a series
of 2.5 mm by 13 mm (0.1 in. by 0.5 in.) rectangular slots
along the test sample, at 300 mm (1 ft) intervals progressing
successively 90 degrees around the circumference of the wire.
Assure that the wire core is exposed at each slot by slitting
the inner jacket and core wrap if present. Place the prepared
sample in a dry vessel which when filled will maintain a one
meter (3 ft) head of water over 6 m (20 ft) of uncoiled wire.
Extend and fasten the ends of the wire so they will be above
the water line and the pairs are rigidly held for the duration
of the test.
3.2.3 Capacitance and Conductance Testing:
Measure the initial values of mutual capacitance and conductance
of all pairs in each wire at a frequency of 1 kHz before filling
the vessel
with water. Be sure the wire shield is grounded
to the test equipment. Fill the vessel until there is a one
meter (3 ft) head of water on the wires.
3.2.3.1 Remeasure the mutual capacitance and
conductance after the wires have been submerged for 24 hours
and again after
30 days.
3.2.3.2 Record each sample separately on the
suggested formats attached in Paragraph 5 of this appendix
or on other easily readable formats.
3.2.4. Overall Electrical Deviation
3.2.4.1 Calculate the percent change in all
average parameters between the final parameters after conditioning
with the initial parameters in Paragraph 3.2.3 of this appendix.
3.2.4.2 The stability of the electrical parameters
after of the test must be within the following prescribed
limits:
a. Capacitance: The average mutual capacitance
must be
within 5 percent of its original value; and
b. Conductance: The average mutual conductance
must
not exceed 2 micromhos/kilometer (3.3 micromhos/mile)
at a frequency of 1 kHz.
3.3 Water Penetration Testing
3.3.1 A watertight closure must be placed
over the jacket of length C. The closure must not be placed
over the jacket so tightly that the flow of water through
pre-existing voids or air spaces is restricted. The other
end of the sample must remain open.
3.3.2 Test as per Option A or Option B.
3.3.2.1 Option A: Weigh the sample and closure
prior to testing. Fill the closure with water and place under
a continuous pressure of 10 + 0.7 kPa (1.5 + 0.1 psig) for
one hour. Collect the water leakage from the end of the test
sample during the test and weigh to the nearest 0.1 g. Immediately
after the one hour test, seal the ends of the wire with a
thin layer of grease and remove all visible water from the
closure, being careful not to remove water that penetrated
into the core during the test. Reweigh the sample and determine
the weight of water that penetrated into the core. The weight
of water that penetrated into the core must not exceed 1 gram.
3.3.2.2 Option B: Fill the closure with a
0.2 g sodium fluorscein per liter water solution and apply
a continuous pressure of 10 + 0.7 kPa (1.5 + 0.1 psig) for
one hour. Catch and weigh any water that leaks from the end
of the wire during the one hour period. If no water leaks
from the sample, carefully remove the water from the closure.
Then carefully remove the outer jacket, shield, inner jacket
and core wrap, if present, one at a time, examining with an
ultraviolet light source for water penetration. After removal
of the inner jacket
and core wrap, if present, carefully dissect
the core and examine for water penetration within the core.
Where water penetration is observed, measure the penetration
distance. The distance of water penetration into the core
must not exceed 127 mm (5.0 in.).
3.4 Insulation Compression Test
3.4.1 Test Sample D. Remove inner and outer
jacket, shield
and core wrap, if present, being careful not
to damage the conductor insulation. Remove one pair from the
core and carefully separate, wipe off core filler and straighten
the insulated conductors. Retwist the two insulated conductors
together under sufficient tension to form 10 evenly spaced
360 degree twists in a length of 100 mm (4 in.).
3.4.2 Sample Testing: Center the mid 50 mm
(2 in.) of the twisted pair between two smooth rigid parallel
metal plates measuring 50 mm (2 in.) in length or diameter.
Apply a 1.5
volt dc potential between the conductors,
using a light or
buzzer to indicate electrical contact between
the conductors. Apply a constant load of 67 N (15 lbf) on
the sample for one minute and monitor for evidence of contact
between the conductors. Record results on suggested formats
attached
in Paragraph 5 of this appendix or on other
easily readable formats.
3.5 Jacket Slip Strength Test
3.5.1 Sample Selection: Test sample E from
Paragraph 3.1.1
of this specification.
3.5.2 Sample Preparation: Prepare test sample
in accordance with the procedures specified in ASTM D 4565-90a.
3.5.3 Sample Conditioning and Testing: Remove
the sample from the tensile tester prior to testing and condition
for one hour
at 50 + 2°C. Test immediately in accordance
with the procedure specified in ASTM D 4565-90a. A minimum
outer jacket slip strength of 67 N (15 lbf) is required. Record
the load attained.
3.6 Humidity Exposure
3.6.1 Repeat steps 3.1.1 through 3.1.3.3 of
this appendix for separate set of samples B, C, D and E which
have not been subjected to prior environmental conditioning.
3.6.2 Immediately after completing the measurements,
expose
the test sample to 100 temperature cyclings.
Relative humidity within the chamber must be maintained at
90 + 2 percent. One cycle consists of beginning at a stabilized
chamber and test sample temperature of 52 + 1°C, increasing
the temperature to
57 + 1°C, allowing the chamber and test
samples to stabilize
at this level, then dropping the temperature
back to
52 + 1°C.
3.6.3 Repeat steps 3.1.4.2 through 3.5.3 of
this appendix.
3.7 Temperature Cycling
3.7.1 Repeat steps 3.1.1 through 3.1.3.3 of
this appendix for separate set of samples B, C, D and E which
have not been subjected to prior environmental conditioning.
3.7.2 Immediately after completing the measurements,
subject the test sample to 10 cycles of temperature between
-40°C and +60°C. The test sample must be held at each
temperature extreme for a minimum of 1 1/2 hours during each
cycle of temperature. The air within the temperature cycling
chamber must be circulated throughout the duration of the
cycling.
3.7.3 Repeat steps 3.1.4.2 through 3.5.3 of
this appendix.
4. CONTROL SAMPLE
4.1 Test Samples: A separate set of lengths
for samples A, C, D, and E must have been maintained at 23
+ 3°C for at least
48 hours before the testing.
4.2 Repeat steps 3.2 through 3.5.3 of this
appendix except use length A instead of length B.
4.3 Surge Test
4.3.1 One length of sample F must be used
to measure the breakdown between conductors while the other
length of F must
be used to measure core to shield breakdown.
4.3.2 The samples must be capable of withstanding,
without damage, a single surge voltage of 20 kV peak between
conductors, and 35 kV peak between conductors and the shield
as hereinafter described. The surge voltage must be developed
from a capacitor discharge through a forming resistor connected
in parallel with the dielectric of the test sample. The surge
generator constants must be such as to produce a surge of
1.5 x 40 microseconds wave shape.
4.3.3 The shape of the generated wave must
be determined at a reduced voltage by connecting an oscilloscope
across the forming resistor with the wire sample connected
in parallel with the forming resistor. The capacitor bank
is charged to the test voltage and then discharged through
the forming resistor and
test sample. The test sample will be considered
to have passed the test if there is no distinct change in
the wave shape obtained with the initial reduced voltage compared
to that obtained after the application of the test voltage.
5. TEST DATA FORMATS
5.1 The following suggested formats may be
used for submitting the test data to REA.
ENVIRONMENTAL CONDITIONING
FREQUENCY 1 kHz
PAIR CAPACITANCE CONDUCTANCE
NUMBER nF/km (nF/mile) micromhos/km (micromhos/mile)
Initial Final Initial Final
1 _____
2 _____
3 _____
_
Average x _____
Overall Percent
Difference in ____________ ____________
Average x
ENVIRONMENTAL CONDITIONING
FREQUENCY 150 kHz
PAIR CAPACITANCE CONDUCTANCE ATTENUATION
NUMBER nF/km (nF/mile) micromhos/km (micromhos/mile)
dB/km (dB/mile)
Initial Final Initial Final Initial Final
1 _______ _____ _______ _____
2 _______ _____ _______ _____ _______ _____
3 _______ _____ _______ _____
_
Average x _______ _____ _______ _____
Overall Percent
Difference in ________ __________ __________
Average x
ENVIRONMENTAL CONDITIONING
WATER IMMERSION TEST (1 kHz)
PAIR CAPACITANCE CONDUCTANCE
NUMBER nF/km (nF/mile) micromhos/km ( micromhos/mile)
Initial 24 hours Final Initial 24 hours Final
1 _____
2 _____
3 _____
_
Average x _____
Overall Percent
Difference in ________________ ______________
Average x
WATER PENETRATION TEST
Option A Option B
End Leakage Weight Gain End Leakage Penetration
g g g mm ( in. )
Control ___________ __________ __________
___________
Heat Age ___________ __________ __________
___________
Humidity
Exposure ___________ __________ __________
___________
Temperature
Cycling ___________ __________ __________
___________
INSULATION COMPRESSION
Failures
Control ________
Heat Age ________
Humidity Exposure ________
Temperature Cycling ________
JACKET SLIP STRENGTH @ 50°C
Load in N (1bf)
Control _______________
Heat Age ________________
Humidity Exposure ________________
Temperature Cycling ________________
FILLER EXUDATION (g)
Heat Age ________________
Humidity Exposure ________________
Temperature Cycle ________________
SURGE TEST (kV)
Conductor to Conductor ______________
Shield to Conductors ______________
united stated department of agriculture
Rural Electrification Administration
APPENDIX B
Sheath Slitting Cord Qualification
1. The test procedures described in this appendix
are for qualification of initial and subsequent changes in
sheath slitting cords.
2. SAMPLE SELECTION: All testing must be performed
on two 1.2 m (4 ft) length of wire removed sequentially from
the same 3 pair, 22 gauge jacketed wire. This wire must not
have been exposed to temperatures in excess of 38°C since
its initial cool down after sheathing.
3. TEST PROCEDURE
3.1 Using a suitable tool, expose enough of
sheath slitting cord to permit grasping with needle nose pliers.
3.2 The prepared test specimens shall be maintained
at a temperature of 23 + 1°C for at least 4 hours immediately
prior to and during the test.
3.3 Wrap the sheath slitting cord around the
plier jaws to ensure a good grip.
3.4 Grasp and hold the wire in a convenient
position while gently and firmly pulling the sheath slitting
cord longitudinally in the direction away from the wire end.
The angle of pull may vary to any convenient and functional
degree. A small starting notch is permissible.
3.5 The sheath slitting cord is considered
acceptable if the cord can slit the jacket and/or shield for
a continuous length
of 0.6 m (2 ft) without breaking the cord.
united states department of agriculture
Rural Electrification Administration
APPENDIX C
Thermal Reel Wrap Qualification
1. The test procedures described in this appendix
are for qualification of initial and subsequent changes in
thermal reel wraps.
2. SAMPLE SELECTION: All testing must be performed
on two
450 mm (18 in.) lengths of wire removed sequentially
from the same 3 pair, 22 gauge jacketed wire. This wire must
not have been exposed to temperatures in excess of 38°C
since its initial cool down after sheathing.
3. TEST PROCEDURE
3.1 Place the two samples on an insulating
material such as wood, etc.
3.2 Tape thermocouples to the jackets of each
sample to measure the jacket temperature.
3.3 Cover one sample with the thermal reel
wrap.
3.4 Expose the samples to a radiant heat source
capable of heating the uncovered jacket sample to a minimum
of 71°C.
A 600 watt photoflood lamp or an equivalent
lamp having the
light spectrum approximately that of the sun
shall be used.
3.5 The height of the lamp above the jacket
shall be 380 mm
(15 in.) or a height that produces the 71°C
jacket temperature on the unwrapped sample.
3.6 After the samples have stabilized at the
temperature, the jacket temperatures of the samples must be
recorded after one hour of exposure to the heat source.
3.7 Compute the temperature difference between
the jackets.
3.8 For the thermal reel wrap to be acceptable
to REA, the temperature differences between the jacket with
the thermal
reel wrap and the jacket without the reel
wrap must be greater than or equal to 17°C.
CLICK
HERE FOR PRINTABLE VERSION
|